The digital control compares the numeric output of the speed sensor to the
numeric number of the speed reference at the summing junction. If the speed is
lower or higher than the reference, a response calculated by the PID
(Proportional-Integral-Derivative control) is sent to the actuator driver calling for
an increase or decrease in actuator current.
The actuator responds to the signal from the actuator driver by repositioning the
fuel or steam rack, changing the speed of the prime mover until the speed signal
and the reference are equal.
A failed speed signal circuit monitors the speed signal input. When no signal is
detected, it calls for minimum fuel. The minimum fuel signal is sufficient to cause
the actuator to go to the minimum position if not restricted. However, due to
linkage adjustment or other restrictions in the external system, minimum actuator
position may not permit prime mover shutdown.
For controls with actuator current of 20 to 160 mA, minimum fuel is defined as:
Actuator current less than 10 mA for forward-acting controls
Actuator current greater than 180 mA for reverse-acting controls
A contact to override the failed speed signal circuit can be connected in series
with terminal 32. Temporarily closing the contact overrides the failed speed
signal circuit as may be required for start-up.
Control Dynamics
RESET, GAIN, and ACTUATOR COMPENSATION adjust the control to
accommodate various types of prime mover systems. RESET adjustment affects
prime mover reaction time when recovering after a sudden load change. The
magnitude of the speed change resulting from a sudden change in load is
controlled by adjusting the GAIN. ACTUATOR COMPENSATION compensates
for the time the actuator and prime mover fuel system takes to react to signals
from the control.
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...