2301D/2301D-EC Digital Control
Manual 26247
46
Woodward
02 DELAY DYN 2 ENABLE (SEC)
dflt = 0.00 (0.00, 20.00)
A delay time, in seconds, that dynamics #1 will continue to be used by the speed
control after the CB contact.
03 DELAY DYN 1 ENABLE (SEC)
dflt = 0.00 (0.00, 20.00)
The delay time that dynamics #2 will continue to be used before switching to
dynamics #1.
04 BREAKPOINT 2A (%LD OR RPM)
dflt = 99.60 (0.01, 5000.00)
05 GAIN @BREAKPOINT 2A
dflt = 4.0 (0.01, 100.00)
06 BREAKPOINT 2B (%LD OR RPM)
dflt = 99.70 (0.01, 5000.00)
07 GAIN @BREAKPOINT 2B
dflt = 4.0 (0.01, 100.00)
08 BREAKPOINT 2C (%LD OR RPM)
dflt = 99.80 (0.01, 5000.00)
09 GAIN @BREAKPOINT 2C
dflt = 4.0 (0.01, 100.00)
10 BREAKPOINT 2D (%LD OR RPM)
dflt = 99.90 (0.01, 5000.00)
11 GAIN BREAKPOINT 2D
dflt = 4.0 (0.01, 100.00)
12 BREAKPOINT 2E (%LD OR RPM)
dflt = 100.00 (0.01, 5000.00)
13 GAIN BREAKPOINT 2E
dflt = 4.0 (0.01, 100.00)
14 RESET 2
dflt = 2.00 (0.01, 100.00)
15 ACTUATOR COMPENSATION 2
dflt = 12.00 (0.01, 100.00)
16 WINDOW WIDTH 2 (RPM)
dflt = 60.00 (1.00, 200.00)
17 GAIN RATIO 2
dflt = 1.0 (1.00, 10.00)
18 SPEED FILTER FREQ 2 (HZ)
dflt = 20.00 (4.00, 20.00)
19 BUMP ACT TRIG (T THEN F)
dflt = FALSE (FALSE, TRUE)
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...