07 TORQUE LIMIT MIN SPEED
dflt = 100.00 (0.00, 100.00)
This sets the maximum fuel demand at the minimum speed set point.
08 SPEED BRKPOINT TORQ LIM
dflt = 800.00 (0.00, 4000.00)
This sets the speed break point of the TLC. It should be adjusted to the rpm
which represents the torque limit breakpoint.
09 TORQUE LIMIT BREAKPOINT
dflt = 100.00 (0.00, 100.00)
This sets the maximum fuel demand at the speed break point.
10 MAX SPEED TORQUE LIMIT
dflt = 1000.00 (0.00, 4000.00)
This sets the maximum speed point of the TLC. It should be adjusted to the
maximum rpm which represents the maximum fuel break point.
11 TORQUE LIMIT MAX SPEED
dflt = 100.00 (0.00, 100.00)
This sets the maximum fuel demand at the maximum speed point.
M**FUEL LIMITERS 2/2**
01 ENABLE MAP LIMITER ?
dflt = FALSE (TRUE, FALSE)
When set TRUE the Manifold Air pressure limiter is active.
02 PRESSURE X1
dflt = 6.000 (-1000.00, 1000.00)
This sets the pressure at the first breakpoint. The limit on fuel demand below this
point is extrapolated from this point and the pressure X2
below.
03 MAP LIMIT Y1
dflt = 100.000 (0.00, 100.00))
This sets the maximum fuel demand at the first pressure set point.
04 PRESSURE X2
dflt = 8.000 (-1000.00, 1000.00)
This sets the pressure at the second breakpoint.
05 MAP LIMIT Y2
dflt = 100.000 (0.00, 100.00)
This sets the maximum fuel demand at the second pressure set point.
06 PRESSURE X3
dflt = 10.000 (-1000.00, 1000.00)
This sets the pressure at the third breakpoint.
07 MAP LIMIT Y3
dflt = 100.000 (0.00, 100.00)
This sets the maximum fuel demand at the third pressure set point.
08 PRESSURE X4
dflt = 15.000 (-1000.00, 1000.00)
This sets the pressure at the fourth breakpoint.
09 MAP LIMIT Y4
dflt = 100.000 (0.00, 100.00)
This sets the maximum fuel demand at the fourth pressure set point.
10 PRESSURE X5
dflt = 20.000 (-1000.00, 1000.00)
This sets the pressure at the maximum breakpoint.
11 MAP LIMIT Y5
dflt = 100.000 (0.00, 100.00)
This sets the maximum fuel demand at the maximum pressure set point.
12 MAP NEAR FUEL LIMIT %
dflt = 5.000 (0.00, 10.00)
When the maximum air pressure limit comes within the range of this setting the
overload contact is initiated.
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...