Manual 26247
2301D/2301D-EC Digital Control
Woodward
59
U**DISPLAY PID PARAMETERS**
This is a display of the input to the PID control. The values entered in the
Dynamic tuning section are normalized values and the values displayed here can
be used for stability analysis if needed.
01 DYNAMICS 2 ENABLED
(Monitor)
indicates the system is in the isochronous mode (CB aux is closed) and
Dynamics 2 values are input to the PID controller.
02 PID GAIN VALUE
(Monitor)
is the proportional value into the PID.
03 PID INTEGRAL GAIN VALUE
(Monitor)
is the Integral value into the PID, Reset rate.
04 PID SDR VALUE
(Monitor)
is the derivative or lead term into the PID.
V**ANALOG IN/OUTPUT CALIB**
01 AnIN 1, Offset
dflt = 0.000 (-100.00, 100.00)
Sets the offset of analog input 1.
02 AnIN 1, Gain
dflt = 1.000 (0.00, 10.00)
Sets the gain for analog input 1.
03 AnIN 1, mA / Volt
(Monitor)
Shows the actual input value for input 1.
04 AnIN 2, Offset
dflt = 0.000 (-100.00, 100.00)
Sets the offset of analog input 2.
05 AnIN 2, Gain
dflt = 1.000 (0.00, 10.00)
Sets the gain for analog input 2.
06 AnIN 2, mA / Volt
(Monitor)
Shows the actual input value for input 2.
07 Actuator, Offset
dflt = 0.000 (-100.00, 100.00)
Sets the offset for the actuator output.
08 Actuator, Gain
dflt = 1.000 (-100.00, 100.00)
Sets the gain for actuator output.
09 Actuator output
(Monitor)
Shows the actual output value of the actuator.
10 Anout 4 -20 mA, Offset
dflt = 0.000 (-100.00, 100.00)
Sets the offset of analog output.
11 Anout 4 -20 mA, Gain
dflt = 1.000 (-100.00, 100.00)
Sets the gain of analog output.
12 Anout 4 -20 mA, output
(Monitor)
Shows the actual output value.
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...