2301D / 2301D-EC Control Specifications
Woodward Part Numbers:
8273-138
2301D-EC Load Sharing and Speed Control, 24Vdc input, with
Modbus, Ordinary Locations
8273-139
2301D-EC Load Sharing and Speed Control, 24Vdc input, with
Modbus, Hazardous Locations
8273-140
2301D Load Sharing and Speed Control, 24Vdc input, Ordinary
Locations
8273-141
2301D Load Sharing and Speed Control, 24Vdc input, Hazardous
Locations
8923-932
Watch Window Installation
Power Supply Rating
18–40 Vdc (SELV)
Power Consumption
less than or equal 20 W nominal
Input Supply Voltage
Input Supply Current
18 V
589 mA
24 V (nominal)
431 mA
32 V
319.6 mA
Inrush Current
7 A for 0.1 ms (low-voltage model)
Inrush Current
22 A for 15 ms (high-voltage model)
Steady State Speed Band
±0.25% of rated speed
Magnetic Pickup
100–25 000 Hz (300–3600 rpm)
Discrete Inputs (8)
3 mA at 24 Vdc, impedance approximately 5.2 k
Remote Reference Input
0–20 mA, 4–20 mA, 0–5 Vdc, 1–5 Vdc, or ±2.5 Vdc externally
powered
SPM-A Input
±2.5 Vdc, externally powered
Analog Output #1
0–20 mA, 4–20 or 0–200 mA to actuator, software configurable
Analog Output #2
0–20 or 4–20 mA , internally powered, configurable
Discrete Outputs (4)
power by ex12 Vdc or +24 Vdc source, max output current
200 mA
Discrete Output Ratings
Low-side drivers with overvoltage protection, 200 mA maximum
Communication Port (J2)
RS-232, RS-422, 9-pin connector, 1200 to 38 400 baud, full duplex
Ambient Operating Temperature
–40 to +70 °C (–40 to +158 °F)
Storage Temperature
–40 to +105 °C (–40 to +221 °F)
Humidity
Lloyd’s Register of Shipping, Test Specification No. 1, 1996,
Humidity Test 1, 95% at +20 to +55 °C (+68 to +131 °F) condensing
Mechanical Vibration
Lloyd’s Register of Shipping, Test Specification No. 1, Vibration Test
2 (5–25 Hz, ±1.6 mm, 25–100 Hz, ±4.0 g)
Mechanical Shock
US MIL-STD 810C, Method 516.2, Procedure I (basic design test),
Procedure II (transit drop test, packaged), Procedure V (bench
handling)
Equipment Classification
Class 1 (grounded equipment)
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...