Manual 26247
2301D/2301D-EC Digital Control
Woodward
113
SERVICE MENU
PROGRAMMED
VALUE
DEFAULT
VALUE
TUNABLE RANGE
MIN.
MAX.
11 UNLOADING RATE (KW/SEC)
20.000
1.00
600.00
12 ENABLE FAST LOAD RATE
FALSE
TRUE
FALSE
13 FAST RAMP ENABLE LOAD(%)
80.000
1.00
110.00
14 FAST RAMP RATE (KW/SEC)
60.000
1.00
600.00
O**ACTUATOR BUMP SETUP**
01 ACT BUMP ENABLE
FALSE
TRUE
FALSE
02 ACT BUMP LEVEL (%FD)
1.000
0.00
25.00
03 ACT BUMP DURATION (SEC)
0.110
0.08
2.00
04 BUMP ACT TRIG (T THEN F)
FALSE
TRUE
FALSE
P**ANALOG INPUTS SETTINGS**
01 AI 1 CONFIGURED FOR:
Monitor
02 AI 2 CONFIGURED FOR:
Monitor
03 SPEED w/ RMT IN@MIN(RPM)
800.000
0.00
4000.00
04 SPEED w/ RMT IN@MAX(RPM)
1000.000
0.00
4000.00
05 RMT SPEED REF INPUT(RPM)
Monitor
06 RMT SPDREF INC TIME(SEC)
30.000
1.00
300.00
07 RMT SPDREF DEC TIME(SEC)
30.000
1.00
300.00
08 BSLOAD w/RMT IN@MIN (KW)
20.000
0.00
30000.00
09 BSLOAD w/RMT IN@MAX (KW)
90.000
10.00
30000.00
10 RMT BSLOAD REF INPUT(KW)
Monitor
11 RMT BSLOAD INC TIME(SEC)
60.000
1.00
600.00
12 RMT BSLOAD DEC TIME(SEC)
60.000
1.00
600.00
13 REMOTE AUX SCALE(%/VOLT)
3.000
0.10
5.00
14 SYNC INPUT SCALE(%/VOLT)
0.700
0.10
5.00
15 MAP LIMITER INPUT MIN
0.000
-10000.0
10000.0
16 MAP LIMITER INPUT MAX
20.000
-10000.0
10000.0
Q**DISCRETE OUT SETTINGS**
01 RELAY 1 SELECTED AS
Monitor
02 RELAY 1 LEVEL SW (1-6)
1
1
6
03 RELAY 1 LEVEL SELECT FOR
Monitor
04 RELAY 1 ON LEVEL =
0.000
-32000.00 32000.00
05 RELAY 1 OFF LEVEL =
0.000
-32000.00 32000.00
06 RELAY 2 SELECTED AS
Monitor
07 RELAY 2 LEVEL SW (1-6)
1
1
6
08 RELAY 2 LEVEL SELECT FOR
Monitor
09 RELAY 2 ON LEVEL =
0.000
-32000.00 32000.00
10 RELAY 2 OFF LEVEL=
0.000
-32000.00 32000.00
11 RELAY 3 SELECTED AS
Monitor
12 RELAY 3 LEVEL SW (1-6)
2
1
6
13 RELAY 3 LEVEL SELECT FOR
Monitor
14 RELAY 3 ON LEVEL =
0.000
-32000.00 32000.00
15 RELAY 3 OFF LEVEL =
0.000
-32000.00 32000.00
16 RELAY 4 SELECTED AS
Monitor
17 RELAY 4 LEVEL SW (1-6)
1
1
6
18 RELAY 4 LEVEL SELECT FOR
Monitor
19 RELAY 4 ON LEVEL =
0.000
-32000.00 32000.00
20 RELAY 4 OFF LEVEL =
0.000
-32000.00 32000.00
21 BREAKER OPEN TIME (SEC)
1.000
0.80
60.00
22 RAMP @ MIN,CB DELAY(SEC)
Monitor
R**ANALOG OUTPUT SETTINGS**
01 ANALOG OUTPUT SEL
9
(1-9)
1
1
02 ANALOG OUTPUT SELECTION
Monitor
03 ANOUT, 4 MA OFFSET
0.000
-200.00
200.00
04 ANOUT, 20MA SCALE
100.000
-200.00
200.00
05 ANALOG OUT 1 (%)
Monitor
S**RELAY AND ANOUT TESTS**
01 ENABLE MANUAL DRIVR TEST
FALSE
TRUE
FALSE
02 FORCE OUTPUT STATUS
Monitor
03 TURN ON DO1
FALSE
TRUE
FALSE
04 DISCRETE OUTPUT #1
Monitor
05 TURN ON DO2
FALSE
TRUE
FALSE
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...