Manual 26247
2301D/2301D-EC Digital Control
Woodward
63
11 PARITY
dflt = 1 (1, 3)
Sets the Parity input defines protocol for the parity. If you selected 8 data bits
select '1' for none:
1= OFF (none)
2= ODD
3= EVEN
12 PARITY IS SET FOR
(Monitor)
Shows the parity setting.
13 DRIVER
dflt = 1 (1, 2)
Sets the Driver input defines the type of driver output for this port.
1= RS232
2= RS422
14 DRIVER IS SET FOR
(Monitor)
Shows the selected driver.
15 TIME OUT (SEC)
dflt = 2.000 (0.00, 100.00)
Sets the Time-out Number of Seconds input defines the Modbus link dead time
allowed before a link error occurs.
16 NETWORK ADDRESS
dflt = 1 (1, 247)
Sets the Network Address input defines the slave block address on the Modbus
network. The network address may depend on master device allowable
addresses.
17 ENABLE MODBUS CONTROL
dflt = FALSE (TRUE, FALSE)
When set TRUE you are able to control using Modbus.
18 USE MODBUS ANALOG CNTRL
dflt = FALSE (TRUE, FALSE)
Set this to TRUE if you want to use the analog Modbus speed setting/baseload
reference.
When parameter 18 is set TRUE the analog inputs are disabled. If the
communication fails the speed setting/baseload setting will go to
minimum. The analog settings are not latched to the last value.
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...