SECTION 27: T
ROUBLESHOOTING
159 of 198
Burner (continued)
27.4 Temperature Controls
If temperat
u
re control pro
b
lems occ
u
r and are not
remedied in the tro
ub
leshooting proced
u
re, refer to
the tro
ub
le shooting ta
b
le for the
u
nit specific
temperat
u
re control amplifier.
1. For
u
nits
w
ith the Maxitrol series 14 tempera-
t
u
re controls, refer to the Field Ser
v
ice Check
List for Series 14. Series 14 are s
u
pplied on
u
nits eq
u
ipped
w
ith DAT and DATRO style
remote panels.
2.
For
u
nits
w
ith the Maxitrol series 44 tempera-
t
u
re controls, refer to the Field Ser
v
ice Check
List for Series 44. Series 44 are s
u
pplied on
u
nits eq
u
ipped
w
ith RMTC remote panels.
3.
For
u
nits
w
ith the Maxitrol series 94 tempera-
t
u
re controls, refer to the Field Ser
v
ice Check
List for Series 94. Series 94 are s
u
pplied on
u
nits eq
u
ipped
w
ith WRP style remote panels.
4.
For
u
nits
w
ith the Maxitrol series MP tempera-
t
u
re controls, refer to the Field Ser
v
ice Check
List for Series MP. Series MP are s
u
pplied on
u
nits eq
u
ipped
w
ith WRP remote panels.
If pro
b
lems persist after performing the
tro
ub
leshooting proced
u
re and the temperat
u
re
control tro
ub
leshooting proced
u
re contact the factory.
27.5 Series 14 - Preliminary Circuit Analysis
For ease in tro
ub
leshooting, it is ad
v
isa
b
le to
w
ire the
system as follo
w
s (this differs from the normal
connection).
• The Discharge Air Sensor is disconnected and
replaced
w
ith a 10,000 ohm, 1/2
w
att test resistor
(terminals 3 and 4). If inlet air sensor is
b
eing
u
sed, disconnect and replace
w
ith a j
u
mper. On
u
nits
w
here the Remote Temperat
u
re Selector is
located a considera
b
le distance from the heater, it
may
b
e ad
v
antageo
u
s to connect the selector at
the heater location.
1. Connect a DC
v
olt meter (capa
b
le of reading 0-
24 V DC) on the Mod
u
lator or Mod
u
lator-Reg
u
-
lator Val
v
e terminals. Set the temperat
u
re to
the minim
u
m dial setting. The DC
v
oltage
sho
u
ld read 0
v
olts. The DC
v
oltage sho
u
ld
grad
u
ally increase to at least 20
v
olts as yo
u
slo
w
ly rotate the dial to the maxim
u
m dial set-
ting. If these
v
oltages are o
b
tained, the
v
al
v
e
f
u
nction can no
w
b
e checked o
u
t.
2.
The operation of the Val
v
e
w
ith regard to
v
olt-
age is as follo
w
s: from 0
v
olts to approximately
5
v
olts, the mod
u
lating
v
al
v
e sho
u
ld
b
e on
b
ypass flo
w
w
ith the heater operating on lo
w
or
minim
u
m fire. From approximately 5
v
olts to 15
v
olts DC, the
v
al
v
e sho
u
ld
b
e performing its
mod
u
lating f
u
nction, and the heater sho
u
ld
b
e
firing at a mod
u
lated flo
w
rate
b
et
w
een lo
w
and
high fire, depending
u
pon the
v
oltage. A
b
o
v
e
approximately 15
v
olts DC, the Val
v
e sho
u
ld
b
e
deli
v
ering f
u
ll flo
w
to the heater and the
u
nit
sho
u
ld
b
e on f
u
ll fire. If the DC
v
oltage is
o
b
tained on the Val
v
e terminals,
bu
t the heater
does not respond as descri
b
ed, the pro
b
lem
can
b
e isolated to the
v
al
v
e itself or to the gas
control manifold of the heater.
3.
In the e
v
ent proper
v
oltages are o
b
tained, and
the Val
v
e responds correctly to these DC
v
olt-
ages, the pro
b
lem co
u
ld
w
ell
b
e in the
w
iring
leading to the Discharge Air Sensor or the Dis-
charge Air Sensor itself.
4.
If the proper
v
oltages are not o
b
tained
w
hen
w
ired as instr
u
cted, the pro
b
lem can
b
e iso-
lated to the electronics and this may once
again
b
e re
v
ie
w
ed in the check list.
PROBLEM
POSSIBLE CAUSE
SOLUTION
No main flame
Man
u
al sh
u
t off
v
al
v
e closed
Open man
u
al sh
u
t off
v
al
v
e
Safety Sh
u
t Off Val
v
e not operating. Is there
positi
v
e gas press
u
re do
w
nstream of SSOV?
Check
w
iring from
bu
rner control to
SSOV
Verify inlet gas press
u
re
Replace SSOV
Minim
u
m gas s
u
pply press
u
re
Verify minim
u
m gas s
u
pply press
u
re as
per data plate is a
v
aila
b
le
B
u
rner openings o
b
str
u
cted
Remo
v
e o
b
str
u
ction
Clean
bu
rner orifice holes
Improper
bu
rner lo
w
fire adj
u
stment on mod
u
-
lating
v
al
v
e
Adj
u
st lo
w
fire as per the rele
v
ant Max-
itrol temperat
u
re control instr
u
ctions.
Содержание TT Series
Страница 2: ......
Страница 4: ......
Страница 136: ...TT SERIES INSTALLATION OPERATION AND SERVICE MANUAL 130 of 198 FIGURE 114 Regulator RV61 ...
Страница 167: ...SECTION27 TROUBLESHOOTING 161 of 198 ...
Страница 175: ...SECTION27 TROUBLESHOOTING 169 of 198 ...
Страница 176: ...TT SERIES INSTALLATION OPERATION AND SERVICE MANUAL 170 of 198 27 7 2 Series 94 Field Service Checklist ...
Страница 177: ...SECTION27 TROUBLESHOOTING 171 of 198 ...
Страница 198: ...TT SERIES INSTALLATION OPERATION AND SERVICE MANUAL 192 of 198 ...
Страница 202: ...TT SERIES INSTALLATION OPERATION AND SERVICE MANUAL 196 of 198 ...
Страница 203: ...SECTION 28 THE WEATHER RITE TT SERIES WARRANTY 197 of 198 ...
Страница 204: ...TT SERIES INSTALLATION OPERATION AND SERVICE MANUAL 198 of 198 ...