SECTION 24: S
TART
-
UP
P
ROCEDURES
125 of 198
24.4.1.1 Differential Pressure Adjustment Manual
Profiles
To adj
u
st the differential press
u
re that
w
as meas
u
red
in the step a
b
o
v
e,
u
se the profile damper adj
u
stment
q
u
adrants located a
b
o
v
e and
b
elo
w
the
bu
rner
access panel for horizontal config
u
ration or on either
side of the
bu
rner access panel on
v
ertical
config
u
ration. To increase the differential press
u
re,
t
u
rn the q
u
adrant to
w
ards the centerline of the
bu
rner. To decrease the differential press
u
re, t
u
rn the
q
u
adrants to
w
ards the parallel of airflo
w
path. Both
q
u
adrants m
u
st
b
e at the same setting,
bu
t opposing,
for proper airflo
w
distri
bu
tion across the
bu
rner. Make
any adj
u
stments in small increments and recheck
press
u
re drop after each adj
u
stment.
See Page 124,
Figure 109
.
FIGURE 110: Profile Quadrant Adjustment
24.4.1.2 Differential Pressure Adjustment Motor-
ized Profiles
To adj
u
st the differential press
u
re that
w
as meas
u
red
on Page 124, Section 24.4.1
the profile
b
lade
assem
b
lies m
u
st
b
e adj
u
sted indi
v
id
u
ally to achie
v
e
the desired press
u
re. DO NOT dist
u
r
b
the
relationship of the damper motor to the shaft or any
linkage adj
u
stments. Loosen the setscre
w
nearest
the linkage end of the profile
b
lade and t
u
rn the
b
lade
on the shaft in the direction necessary to correct the
press
u
re, make changes in small increments. Each
profile assem
b
ly is done indi
v
id
u
ally and eq
u
ally,
tighten setscre
w
s sec
u
rely
w
hen done. T
u
rn the air
lea
v
ing edge of
b
lade to
w
ard the
bu
rner to increase
press
u
re and a
w
ay from
bu
rner to decrease
press
u
re. Check press
u
re o
v
er the f
u
ll operating
range of the
u
nit
w
hen done.
See Page 124, Figure
109
FIGURE 111: Motorized Profile Adjustment
24.4.2 Burner Gas Flow (Temperature Rise)
The gas flo
w
m
u
st
b
e adj
u
sted to gi
v
e the design
temperat
u
re rise a
b
o
v
e o
u
tside air. Refer to the air
handler's rating plate for the temperat
u
re rise it
w
as
ordered for. To determine the proper gas flo
w
the
follo
w
ing steps need to
b
e completed.
24.4.2.1 Burner Gas Flow - Maxitrol
®
Series 14/44
Temperature Control System
• Meas
u
re the o
u
tside air temperat
u
re.
• Disconnect one of the discharge sensor
w
ires
from terminal 3 on the Maxitrol 1014 or 1044
amplifier. The air handler
w
ill no
w
r
u
n at high fire.
• Start the air handler in the
w
inter mode.
• After the
bu
rner has ignited and r
u
n for 30
seconds, meas
u
re the discharge temperat
u
re.
• S
ub
tract the o
u
tside air temperat
u
re from the
discharge temperat
u
re; the difference is the
temperat
u
re rise.
• If the
v
al
u
e is lo
w
er than req
u
ired, increase the
gas flo
w
. If the
v
al
u
e is higher than req
u
ired,
decrease the gas flo
w
. For adj
u
stments
See Page
127, Section 24.5
.
Содержание TT Series
Страница 2: ......
Страница 4: ......
Страница 136: ...TT SERIES INSTALLATION OPERATION AND SERVICE MANUAL 130 of 198 FIGURE 114 Regulator RV61 ...
Страница 167: ...SECTION27 TROUBLESHOOTING 161 of 198 ...
Страница 175: ...SECTION27 TROUBLESHOOTING 169 of 198 ...
Страница 176: ...TT SERIES INSTALLATION OPERATION AND SERVICE MANUAL 170 of 198 27 7 2 Series 94 Field Service Checklist ...
Страница 177: ...SECTION27 TROUBLESHOOTING 171 of 198 ...
Страница 198: ...TT SERIES INSTALLATION OPERATION AND SERVICE MANUAL 192 of 198 ...
Страница 202: ...TT SERIES INSTALLATION OPERATION AND SERVICE MANUAL 196 of 198 ...
Страница 203: ...SECTION 28 THE WEATHER RITE TT SERIES WARRANTY 197 of 198 ...
Страница 204: ...TT SERIES INSTALLATION OPERATION AND SERVICE MANUAL 198 of 198 ...