Digital Alarm Sensor Settings
Digital alarms provide warnings of almost any emergency condition you need to be informed about. Any no-
voltage circuit (“dry” contact) that can be switched will provide an alarm to the controller. The term “
digital
”
refers to two possible states for a circuit:
OPEN
and
CLOSED
. Set up each digital alarm input to sense for an
OPEN
or a
CLOSED
circuit.
Trigger Alarm on Active Input
Set this to YES if you want the controller to alarm when the input is active.
DIGITAL ALARM GROUP #1 SETTING Z1-S01
Trigger alarm on Active input: YES
Input is Active When
Set this to
CLOSED
if you want the controller to alarm when the digital input circuit becomes closed. Set this to OPEN
if you want the controller to alarm when the digital input circuit becomes open.
DIGITAL ALARM GROUP #1 SETTING Z1-S01
Input is Active when: CLOSED
Alarm Delay Time
DIGITAL ALARM GROUP #1 SETTING Z1-S01
Alarm Delay Time: 0:30
SYSTEM
SETUP
Input the time (minutes and seconds) the alarm condition must exist before the alarm is triggered. For example, the
controller should alarm when a door is left open. Set the Alarm Delay Time to 30 seconds to prevent a false alarm
from normal building entry and exiting.