Cool Pad, Mister & Fogger Settings
Input the group numbers of the air sensors you want to use for controlling the cool pad, mister or fogger (mister or
fogger is not available as a menu item on some controllers). The controller uses Shared Sensor Technology to average
the temperature readings of any sensors you want to use to control any device.
COOL PAD LOW GROUP #5 SETTING
Z1-S01
Use Sensors: ALL (Avg 74.7)
CONTROL
SETTINGS
DEVICE / EQUIPMENT SETTINGS
Z1-S01
PRESS ENTER TO VIEW SETTINGS
Reminder: The Cool Pad, Mister and Fogger Settings are listed under the DEVICE / EQUIPMENT SETTINGS menu.
The cool pad, mister or fogger (evaporative cooling devices) can be enabled for a certain period of day to prevent
having the device turned on at an undesirable time. The device only operates between the enable and disable times.
The times input here must be in 24 hour clock format.
COOL PAD LOW GROUP #5 SETTING
Z1-S01
Time of Day Enable: 11:40 Disable: 19:00
Evaporative cooling loses its effectiveness as humidity inside the building increases. Input a relative humidity level at
which evaporative cooling should be disabled. Then, input the level at which evaporative cooling will be re-enabled.
COOL PAD LOW GROUP #5 SETTING
Z1-S01
HUMIDITY Disable: 85% ReEnable: 75%
When the humidity reaches the Disable value, the evaporative cooling device remains disabled until the humidity
drops to the ReEnable value. Set the Disable or ReEnable value to 100 percent to have the controller ignore the
disable/re-enable feature entirely.
To use this feature, the controller must have a humidity sensor attached.
Either high temperature or high humidity can stress animals, but a combination of high temperature and high
humidity is very stressful and it can be deadly. The combination of humidity plus temperature is called the
stress index.
Input a stress index level at which evaporative cooling should be disabled. Then, input a stress index level at which
evaporative cooling will be re-enabled.
COOL PAD LOW GROUP #5 SETTING
Z1-S01
TEMP+HUMIDITY Disable: 160 ReEnable 140
A chart on the next page illustrates how combinations of temperature and
humidity produce a Stress Index of 175.
Use Sensors
Time of Day to Enable / Disable
Humidity Disable / Re-Enable
Stress Index Disable