Installation
vacon • 55
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5
Notes:
1) No aggressive water allowed.
2) To avoid corrosion of piping, the sulphate content must not exceed 150 mg/l.
The cleanness of the heat exchanger, and therefore the heat exchanging capacity, depend on the
purity of the process water. The more impure the water, the more frequently the heat exchanger
needs cleaning. The following figures are reference values required of cooling circuit process water:
Table 17. Drinking water quality recommendations
Quality
Unit
Max. value
Aluminium
μg/l
200
Ammonium (NH
4
+
)
mg/l
0.50
Ammonium (NH
4
-N)
mg/l
0.40
Chloride
1]
mg/l
<100
Manganese
μg/l
50
Iron
μg/l
<0.5
Sulphate
1] 2]
mg/l
250
Sodium
mg/l
200
Oxidizability
(COD
Mn
-O
2
)
mg/l
5.0
Quality
Unit
Desired value
Clostridium perfringens
(including spores)
pmy/100 ml
0
Coliform bacteria
pmy/100 ml
0
Bacterial count (22 °C)
No unusual changes
pH
1]
pH
6…8
Electrical conductivity
1]
μS/cm
<100
Turbidity
To be approved by user and
no unusual changes
Colour
No unusual changes
Smell and taste
No unusual changes
Total organic carbon (TOC)
No unusual changes
Tritium
beq/l
100
Indicative total dose
mSv/year
0.10
Water hardness
°dH
3...10
Max. particle size in coolant
μm
300