Control keypad
vacon • 125
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
is 0, the STOP button will stop the motor only when the keypad has been selected as the active
control place.
7.3.4
Active faults menu (M4)
The Active faults menu can be entered from the Main menu by pushing the Menu button right when
the location indication M4 is visible on the first line of the keypad display.
When a fault brings the AC drive to a stop, the location indication F1, the fault code, a short
description of the fault and the fault type symbol (see Chapter 7.3.4.1) will appear on the display. In
addition, the indication FAULT or ALARM (see Figure 60 or Chapter 7.1.1) is displayed and, in case
of a FAULT, the red led on the keypad starts to blink. If several faults occur simultaneously, the list
of active faults can be browsed with the Browser buttons.
The memory of active faults can store the maximum of 10 faults in the order of appearance. The
display can be cleared with the Reset button and the read-out will return to the same state it was
before the fault trip. The fault remains active until it is cleared with the Reset button or with a reset
signal from the I/O terminal or fieldbus.
NOTE!
Remove external Start signal before resetting the fault to prevent unintentional restart of the
drive.
NOTE!
There are some special functions that can be performed when in the M3 menu:
Select the keypad as the active control place by keeping the Start button pushed down for 3
seconds when the motor is running. The keypad will become the active control place and the
current frequency reference and direction will be copied to the keypad.
Select the keypad as the active control place by keeping the Stop button pushed down for 3
seconds when the motor is stopped. The keypad will become the active control place and the
current frequency reference and direction will be copied to the keypad.
Copy the frequency reference set elsewhere (I/O, fieldbus) to the panel by keeping the
pushed down for 3 seconds.
Note that if you are in any other than M3 menu these functions will not work.
If you are in some other than M3 menu and try to start the motor by pressing the START button when
the keypad is not selected as the active control place you will get an error message Keypad Control
NOT ACTIVE.
enter
Normal state,
no faults:
F0
READY
I/Oterm
Active faults
11379_uk