Control keypad
vacon • 123
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
Figure 64. Parameter value change procedure
7.3.3
Keypad control menu (M3)
In the Keypad Controls Menu, you can choose the control place, edit the frequency reference and
change the direction of the motor. Enter the submenu level with the Menu button right.
7.3.3.1
Selection of control place
There are three different places (sources) which the AC drive can be controlled from. For each
control place, a different symbol will appear on the alphanumeric display:
Table 50. Keypad control parameters, M3
Code
Parameter
Min
Max
Unit
Default Cust
ID
Note
P3.1
Control place
1
3
1
125
1
= I/O terminal
2
= Keypad
3
= Fieldbus
R3.2
Keypad reference
Par. 2.1.1
Par.
2.1.2
Hz
P3.3
Direction (on keypad)
0
1
0
123
0
= Forward
1
= Reverse
R3.4
Stop button
0
1
1
114
0
= Limited function of Stop button
1
= Stop button always enabled
Control place
symbol
I/O terminals
Keypad (panel)
Fieldbus
G1 G8
READY
Keypad
P1
P18
READY
Keypad
13.95 Hz
READY
Keypad
G1
G8
Ke ypa d
READY
Keypad
13.95 Hz
enter
READY
Keypad
14.45 Hz
Parameters
Basic parameters
Min Frequency
Input signals
Min Frequency
Min Frequency
11377_uk
I/O term
Keypad
Bus/Comm