Commissioning
vacon • 145
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
8
b)
Push the Start button on the keypad.
c)
Move over to the Keypad control menu (M3) and Keypad Reference submenu
(Chapter 7.3.3.2) and change the frequency reference using the Browser buttons
d)
Check in the Monitoring menu (M1) that the value of Output frequency changes according
to the change of frequency reference.
e)
Push the Stop button on the keypad.
10. Run the start-up tests without the motor being connected to the process, if possible. If this is
not possible, secure the safety of each test prior to running it. Inform your co-workers of the
tests.
a)
Switch off the supply voltage and wait up until the drive has stopped as advised at
Chapter 8.1, step 5.
b)
Connect the motor cable to the motor and to the motor cable terminals of the AC drive.
c)
See to that all Start/Stop switches are in Stop positions.
d)
Switch the mains ON
e)
Repeat test 9A or 9B.
11. Connect the motor to the process (if the startup test was run without the motor being con
nected).
a)
Before running the tests, make sure that this can be done safely.
b)
Inform your co-workers of the tests.
c)
Repeat test 9A or 9B.
+
-