Non-regenerative front end
vacon • 191
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
11
P2.2.1.2
BreakerFeedback
0
59
11
1916
Select digital input signal for
Breaker Feedback
P2.2.1.3
Miss Input Phase
0
59
12
1917
Select digital input for missing
input phase or low input voltage
P2.2.1.4
External Fault
0
59
13
1918
Select for digital input signal
external fault ,normal open logic
P2.2.1.5
Choke Temp
0
59
14
1919
Select for digital input Choke
Temp
P2.2.1.6
Fault Reset
0
59
15
1920
Select for digital input signal fault
reset
P2.2.1.7
E Stop
0
59
42
1921
Select for digital input signal E-
stop feedback
P2.2.1.8
Cooling OK
0
59
43
1922
Select for digital input signal
liquid cooling feedback
P2.2.1.9
Fan Sensor 1
0
59
44
1923
Select for digital input signal
cooling fan monitor
P2.2.1.1
0
Fan Sensor 2
0
59
45
1924
Selection of fan sensor2 from
digital input signal, default is from
OPT-B1 DIN.D5
Table 86. Analog input G2.2.2
Code
Parameter
Min
Max
Unit
Default
ID
Desciption
P2.2.2.1
DC Voltage
0
59
10
1925
Selection for analog input of dc
voltage
P2.2.2.2
DC Min Point
0.00
40.00
%
20.00
1926
Percent value corresponds to 0 dc
voltage
P2.2.2.3
Max DC Voltage
500
2000
V
1500
1927
Dc voltage measurement devices
max range
P2.2.2.4
Current
0
59
11
1928
Selection of analog input signal
input current
P2.2.2.5
Current MinPoint
0.00
100.00
%
0.00
1929
Analog input signal min point for
current measurement
P2.2.2.6
Max Current
0
32000
A
1000
1930
Max current corresponds to max
analog input 100.00%
P2.2.2.7
Unit Temp
0
59
30
1931
Selection of analog input for
heatsink Temp
P2.2.2.8
Choke Temp 1
0
59
31
1932
Select analog input signal for
choke temp 1 from pt100 signal
P2.2.2.9
Choke Temp 2
0
59
32
1933
Select analog input signal for
choke temp 2 from PT100 signal
Table 85. Digital input G2.2.1
Code
Parameter
Min
Max
Unit
Default
ID
Desciption