Non-regenerative front end
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
11.13
Parameters
The parameters for software version ANCNQ100 are described below.
Table 83. Monitoring values
Code
Parameter
Min
Max
Unit
Default
ID
Desciption
V1.2.1
DC Voltage
0
1500
V
0
7
DC voltage measured by external
AI devices
V1.2.2
Current
0
5000
A
0
3
Current measured by external AI
devices
V1.2.3
Unit Temperature
-30.0
200.0
deg
0.0
8
Heatsink temp measured by
PT100 signal
V1.2.4
Choke Temp 1
-30.0
200.0
deg
0.0
50
Choke temp 1 measured by PT100
V1.2.5
Choke Temp 2
-30.0
200.0
deg
0.0
43
Choke temp 2 measured by
second PT100
V1.2.6
Status Word
0
65535
0
20
B0 =PrechargeReady
B1 =MC RUN
B2 =MC Warning
B3 =MC Fault
B4 =DIN Run
B5 =DIN BreakerFeedback
B6 =DIN MissInputPhase
B7 =DIN ChokeTempFault
B8 =DIN Reset
B9 =DOUT DC Precharging
B10=DOUT Close MCB
B11=DIN Cooling Fan
B12=DIN Cooling Fan2
Bit13=DIN External Fault Close
Bit14=DIN E Stop
Bit15=DIN Cooling OK
V1.2.7
Hour Counter
0
65535
Hour
0
1909 Run Hour counter
Table 84. Basic parameters G2.1
Code
Parameter
Min
Max
Unit
Default
ID
Desciption
P2.1.1
Main Voltage
400
690
V
690
1910 Main supply voltage from network
P2.1.2
PreChargReadyLev
20
100
%
80
1911 Precharge ready level
P2.1.3
MaxChargeTime
0.00
30.00
s
5.00
1912
Max charge time. If the charging
time is more than this, a fault will
generated
P2.1.4
Password
0
65535
0
1913 Password
Table 85. Digital input G2.2.1
Code
Parameter
Min
Max
Unit
Default
ID
Desciption
P2.2.1.1
Run
0
59
10
1915
Select Digital input signal for Run
command