Electrical cabling and connections
vacon • 79
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6
1)
Due to insufficient number of terminal bolt connections for required amount of cables, the cabinet must be
equipped with an external flexible cable connection block at both mains and motor ends if stiff cable type is
used.
Data in Italic refer to drives with 12-pulse supply.
Units with 6-pulse supply
Note that all other sizes have 3 input terminals except for size CH74, which has 9 input terminals.
CH74 cables must be connected symmetrically between 3 parallel connected rectifiers in each
phase.
Units with 12-pulse supply
12-pulse supply can be used with drives of sizes CH72 and CH74. The number of input terminals for
both is 6.
If 12-pulse supply is used, pay also attention to the fuse selection, see page 82 and page 83.
See the tightening torques of bolts in Table 40.
CH74
1)
2060_5
2060
8*(3*185+95)
300 Cu/Al
***
4/M12
CH74
1)
2300_5
2300
9*(3*185+95)
300 Cu/Al
***
6/M12
Table 39. Mains cable sizes, 525—690 V
Chassis
Type
I
th
Mains cable
Cu [mm
2
]
Terminal cable size
Max. number
of cables/
Bolt size
Main terminal
[mm
2
], max.
Earth terminal
[mm
2
]
CH61
0170_6
170
3*95+50
185 Cu/Al
25—95
2/M12
CH61
0208_6
208
3*150+70
185 Cu/Al
25—95
2/M12
CH61
0261_6
261
3*185+95
185 Cu/Al 2
25—95
2/M12
CH72/CH72
0325_6
325
2*(3*95+50)
300 Cu/Al
25—185
2 (or 4)/M12
CH72/CH72
0385_6
385
2*(3*120+70)
300 Cu/Al
25—185
2 (or 4)/M12
CH72/CH72
0416_6
416
2*(3*150+70)
300 Cu/Al
25—185
2 (or 4)/M12
CH72/CH72
0460_6
460
2*(3*185+95)
300 Cu/Al
25—185
2 (or 4)/M12
CH72/CH72
0502_6
502
2*(3*185+95)
300 Cu/Al
25—185
2 (or 4)/M12
CH63
0590_6
0650_6
590
650
2*(3*240+120)
300 Cu/Al
****
2/M12
CH63
1)
0750_6
750
3*(3*185+95)
300 Cu/Al
****
2/M12
CH74
0820_6
820
3*(3*185+95)
300 Cu/Al
***
6/M12
CH74
0820_6
820
4*(3*150+70)
300 Cu/Al
***
4/M12
CH74
0920_6
920
3*(3*240+120)
300 Cu/Al
***
6/M12
CH74
0920_6
920
4*(3*185+95)
300 Cu/Al
***
4/M12
CH74
1030_6
1030
6*(3*95+50)
300 Cu/Al
***
6/M12
Table 38. Mains cable sizes for AC drives, 400—500 V
Chassis
Type
I
th
Mains cable
Cu [mm
2
]
Terminal cable size
Max. number
of cables/
Bolt size
Main terminal
[mm
2
], max
Earth terminal
[mm
2
]