5
vacon • 72
Installation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Figure 35. Example of input chokes for VACON
®
NX Liquid-Cooled. Sizes 261 A…1150 A
If you have ordered the input chokes for VACON
®
NX Liquid-Cooled separately pay attention to the
following instructions:
1.
Protect the chokes from dripping water. You may even need to use plexiglass for
protection because jets of water may occur when working with the connections.
2.
Connection of cables:
Types CHK0023N6A0, CHK0038N6A0, CHK0062N6A0 (chokes with terminal blocks)
The terminals are marked with letters U,V, W and X,Y and Z in such an order, however,
that terminals U and X, V and Y as well as W and Z form pairs of which one is an input and
the other an output. Furthermore, terminals U,V and W must all be used as either input
or output. The same applies to terminals X, Y and Z. See Figure 33.
Table 34. Choke dimensions; Sizes 261 A…1150 A
Choke type
H1
[mm]
H2
[mm]
W1
[mm]
W2
[mm]
W3
[mm]
W4
[mm]
D1
[mm]
D2
[mm]
D3
[mm]
S1
S2
Ø
Weight
[kg]
CHK0261N6A0
319
357
354
150
275
120
230
206
108
9*14
(8 pcs)
9*14
(9 pcs)
53
CHK0400N6A0
383
421
350
150
275
120
262
238
140
9*14
(8 pcs)
11*15
(9 pcs)
84
CHK0520N6A0
399
446
497
200
400
165
244
204
145
Ø13
(8 pcs)
11*15
(9 pcs)
115
CHK0650N6A0
449
496
497
200
400
165
244
206
145
Ø13
(8 pcs)
11*15
(9 pcs)
130
CHK0750N6A0
489
527
497
200
400
165
273
231
170
Ø13
(8 pcs)
13*18
(9 pcs)
170
CHK0820N6A0
491
529
497
200
400
165
273
231
170
Ø13
(8 pcs)
13*18
(9 pcs)
170
CHK1030N6A0
630
677
497
200
400
165
307
241
170
Ø13
(8 pcs)
13*18
(36 pcs)
213
CHK1150N6A0
630
677
497
200
400
165
307
241
170
Ø13
(8 pcs)
13*18
(36 pcs)
213
1
1
1
3
3
3
2
2
2
W1
H1 H2
W2
W3
W4
W4
D1
D2
D3
S1
S2
nxw12.fh11
Terminal numbers
11343_uk
Table 33.
Supply voltage
AC drive
connection
(terminal no.)
400-480 Vac
2
500 Vac
3
525-690 Vac
3