Electrical cabling and connections
vacon • 91
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6
6.1.6
Installation space
Enough free space must be left above and below the AC drive/inverter to ensure practical and
appropriate electrical and cooling connections. The minimum dimensions are given in the table
below. The space left and right to the drive may be 0 mm.
6.1.7
Grounding of power unit
The mains cables are connected to the protective earth of the switchgear enclosure.
We recommend to connect the motor cables to the common PE of the cabinet/cabinet system.
For grounding of the drive itself, use the grounding terminal on the drive mounting plate (see
Figure 39) and tighten the grounding bolt to 13.5 Nm.
Figure 39. Grounding terminal on mounting plate
Table 45. Installation space
Chassis
A
[mm]
B
[mm]
CH3
100
150
CH4
100
200
CH5
100
200
CH61
100
300
CH62
100
400*
CH63
200
400*
CH64
200
500*
CH72
200
400*
CH74
200
500*
*Distance to the cable connection block.
Additional space must be reserved for
possibly used ferrite rings. See
Chapter 6.1.1.2.
A
B
11347_00
11348 00