Active front end - fuse selection
AC fuses are used to protect the input network in case the Active Front End unit or the LCL filter is
faulty. DC fuses are used to protect the Active Front End unit and the LCL filter in case there is a
short circuit in the DC buses. If DC fuses are not used, short-circuit in the DC buses will cause a
loading of the Active Front End unit. Vacon Ltd will not assume any responsibility for damages
caused by insufficient protection.
The warranty becomes void if the drive is not equipped with
appropriate fuses.
Fuse information
The values in tables are based on max ambient temperature of +50 ºC.
Fuse sizes can differ in the same chassis. Make sure that the Isc of the supply transformer is high
enough to burn fuses fast enough.
Check the current rating of the fuse bases according to the input current of the drive.
The physical size of the fuse is chosen on the basis of the fuse current: Current < 250 amps (size 1
fuse), current > 250 amps (size 3 fuse).
The aR fuses are thermally rated into switch fuse in 50 degree ambient temperature.
The required AC fuse selection for the active front end unit can be found fromTable 66 and Table 67.
The required DC fuse selection for the active front end unit can be found from Table 38 and Table 39.
10.7.1
Fuse sizes, Active Front End units (AC supply)
Table 66. Fuse sizes for VACON
®
NX AFE units (380—500V)
Chassis
Type
I
th
[A]
Fuse
size
DIN43620
‘TTF’ threaded
end
‘TTF’ threaded
end
Qty. of
fuses /
drive 3~
aR fuse part nr.
aR fuse part nr.
aR fuse part nr.
CH3
0016
16
DIN000
NH000UD69V40PV
PC30UD69V50TF
-
3
CH3
0022
22
DIN000
NH000UD69V40PV
PC30UD69V50TF
-
3
CH3
0031
31
DIN000
NH000UD69V63PV
PC30UD69V63TF
-
3
CH3
0038
38
DIN000
NH000UD69V100PV
PC30UD69V100TF
-
3
CH3
0045
45
DIN000
NH000UD69V100PV
PC30UD69V100TF
-
3
CH3
0061
61
DIN00
NH00UD69V125PV
PC30UD69V125TF
-
3
CH4
0072
72
DIN00
NH00UD69V200PV
PC30UD69V200TF
-
3
CH4
0087
87
DIN00
NH00UD69V200PV
PC30UD69V200TF
-
3
CH4
0105
105
DIN00
NH00UD69V200PV
PC30UD69V200TF
-
3
CH4
0140
140
DIN1
NH1UD69V315PV
PC30UD69V315TF
-
3
CH5
0168
168
DIN1
NH1UD69V315PV
PC30UD69V315TF
-
3
CH5
0205
205
DIN1
NH1UD69V400PV
PC30UD69V400TF
-
3
CH5
0261
261
DIN2
NH2UD69V500PV
PC31UD69V500TF
-
3
CH61
0300
300
DIN3
NH3UD69V630PV
PC32UD69V630TF
-
3
CH61
0385
385
DIN3
NH3UD69V630PV
PC32UD69V630TF
-
3
CH62
0460
460
DIN3
NH3UD69V1000PV
PC33UD69V1000TF
-
3
CH62
0520
520
DIN3
NH3UD69V1000PV
PC33UD69V1000TF
-
3
CH62
0590
590
DIN3
PC73UB69V1100PA
PC33UD69V1100TF
-