Non-regenerative front end
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
60
Cooling
Cooling OK digital input for liquid cooling
feedback have triggered the fault
•
Check liquid cooling
•
Check the signal
wiring
•
Check Cooling OK
input
63
EmergencyStop
E-stop digital input for emergency stop
feedback have triggered the fault
•
Check Main Circuit
Breaker functionality
•
Check signal wiring
64
Breaker Trip
MCBs Feedback signal missing after set-
tled time defined with parameter
Breaker Ack Time P2.4.6.
•
Check Main Circuit
Breaker functionality
•
Check signal wiring
Table 96. Fault codes
Fault
code
Fault
Possible cause
Correcting measures