Active front end (NXA)
vacon • 163
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
10
10.6.3
Power rating and dimensions
Figure 88. Example of L
net
choke of a VACON
®
RLC filter
Table 64. VACON
®
RLC ratings, drive suitable and dimensions
VACON
®
NX Liquid-Cooled regenerative line filters - IP00
LCL filter
type
Thermal
current
I
th
[A]
Power loss
c/a/T*)
[kW]
Suitability
[Drive/
voltage:(current)
]
Dimensions
L
net
, 1pcs
WxHxD [mm]
Dimensions
Ldrive, 1pcs
(total 3pcs),
WxHxD
[mm]
Dimensions
C
bank
, 1pcs
WxHxD [mm]
Total
Weight
[kg]
RLC-
0385-6-0
385
2.6/0.8/3.4
CH62/690 VAC:
325 A & 385 A
580 x 450 x 385 410 x 415 x 385 360 x 265 x 150
458
RLC-
0520-6-0
520
2.65/0.65/
3.3
CH62/500-690
VAC
580 x 450 x 385 410 x 415 x 385 360 x 265 x 150
481
RLC-
0750-6-0
750
3.7/1/4.7
CH62/500 VAC,
CH63/690 VAC
580 x 450 x 385 410 x 450 x 385 360 x 275 x 335
508
RLC-
0920-6-0
920
4.5/1.4/5.9
CH63/500 VAC,
CH64/690 VAC
580 x 500 x 390 410 x 500 x 400 360 x 275 x 335
577
RLC-
1180-6-0
1180
6.35/1.95/
8.3
CH63/500 VAC,
CH64/690 VAC
585 x 545 x 385 410 x 545 x 385 350 x 290 x 460
625
RLC-
1640-6-0
1640
8.2/2.8/11
CH64/500-690
VAC
585 x 645 x 385 420 x 645 x 385 350 x 290 x 460
736
RLC-
2300-5-0
2300
9.5/2.9/12.4
CH64/500 VAC:
2060 A & 2300 A
585 x 820 x 370 410 x 820 x 380 580 x 290 x 405
896
Lifting points
25
L3
in
/L3
out
10 15
L2
in
/L2
out
L1
in
/L1
out
L1
out
/L1
in
L1
out2
/L1
in2
L2
out
/L2
in
L2
out2
/L2
in2
L3
out
/L3
in
H
W
D
L3
out2
/L3
in2
3069A_uk
CONNECTION:
In/Out (Always
connected)
400-500V In/Out
(L_in/L_out)
525-690V In/Out
(L_in2/L_out2)
Содержание NX
Страница 1: ...vacon nx ac drives liquid cooled drives user manual ...