Control keypad
vacon • 119
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
7.2.1.1
Swap between keypad control and another control as active control place
With the I/O terminals or fieldbus selected as the active control place, it is also possible to change
the control to the local keypad and back to the original control place.
Irrespective of your location in the menu structure, keep the
button pushed down for 5 seconds.
This will activate the Start & Stop keypad control. The display will jump to the editing mode of
R3.2
Keypad Reference
and you will be able to enter the desired frequency on the keypad. Push the start
button to start the drive.
Pushing the
button again for 5 seconds returns the control to the original control place (active
control place, P3.1) and its reference.
NOTE:
The motor starts if the start command of the active
control place is ON and run at the formerly set reference. The keypad display will show monitoring
value
V1.1 Output Frequency
.
If any of the parameter values in menu M3 is changed in between the swapping the keypad reference
will be reset to 0.00 Hz.
7.3
Navigation on the control keypad
The data on the control keypad are arranged in menus and submenus. The menus are used for
example for the display and editing of measurement and control signals, parameter settings
(Chapter 7.3.2), reference values and fault displays (Chapter 7.3.4). Through the menus, you can
also adjust the contrast of the display (page 137).
The first menu level consists of menus M1 to M7 and is called the Main menu. The user can navigate
in the main menu using the Browser buttons up and down. The desired submenu can be entered
from the main menu using the Menu buttons. When there still are pages to enter under the currently
displayed menu or page, you can see an arrow ( ) in the lower right corner of the display and by
pressing the Menu button right, you can reach the next menu level.
The control keypad navigation chart is shown on the next page. Note that the menu M1 is located in
the lower left corner. From there you will be able to navigate your way up to the desired menu using
the menu and browser buttons.
More detailed descriptions of the menus you will find later in this Chapter.
=
Start button
Pressing this button starts the motor if the keypad is the active control place.
See Chapter 7.3.3.
=
Stop button. Pressing this button stops the motor (unless disabled by
parameter R3.4/R3.6). See Chapter 7.3.3.
V1 V14
READY
Local
RUN
Monitor
Location
Description
Number of items
available; Item value