Electrical cabling and connections
vacon • 77
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6
1)
Due to insufficient number of terminal bolt connections for required amount of cables, the cabinet must be
equipped with an external flexible cable connection block at both mains and motor ends if stiff cable type is
used.
* = Number of bolt connections 2
** = Number of bolt connections 4
*** = Three
grounding
terminals per mounting plate, see Chapter 6.1.7.
**** = Two grounding terminals per mounting plate, see Chapter 6.1.7.
See the tightening torques of bolts in Table 40.
CH62/72
0325_6
325
2*(3*95+50)
**
25—185
4/M12
CH62/72
0385_6
385
2*(3*120+70)
**
25—185
4/M12
CH62/72
0416_6
416
2*(3*150+70)
**
25—185
4/M12
CH62/72
0460_6
460
2*(3*185+95)
**
25—185
4/M12
CH62/72
0502_6
502
2*(3*185+95)
**
25—185
4/M12
CH63
0590_6
590
3*(3*150+70)
**
***
8/M12
CH63
0650_6
650
3*(3*150+70)
**
***
8/M12
CH63
0750_6
750
3*(3*185+95)
**
***
8/M12
CH74
1)
0820_6
820
4*(3*150+70)
**
***
4/M12
CH74
1)
0920_6
920
4*(3*185+95)
**
***
4/M12
CH74
1)
1030_6
1030
4*(3*185+95)
**
***
4/M12
CH74
1)
1180_6
1180
5*(3*185+95)
**
***
4/M12
CH74
1)
1300_6
1300
5*(3*185+95)
**
***
4/M12
CH74
1)
1500_6
1500
6*(3*185+95)
**
***
4/M12
CH74
1)
1700_6
1700
6*(3*240+120)
**
***
4/M12
Table 37. Motor cable sizes, 525—690 V
Chassis
Type
I
th
Motor cable
Cu [mm
2
]
Terminal cable size
Max. number of
cables/
Bolt size
Main terminal
[mm
2
], max
Earth terminal
[mm
2
]