Electrical cabling and connections
vacon • 75
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6
6.1.1.3
Motor cable data
Table 35. Cable types required to meet standards
Cable type
Level N/T
Mains cable
1
Motor cable
1
Control cable
4
1
=
Power cable intended for fixed installation and the specific
mains voltage. Symmetrical shielded cable recommended.
(NKCABLES/MCMK or similar recommended)
4
=
Screened cable equipped with compact low-impedance
shield (NKCABLES /JAMAK, SAB/ÖZCuY-O or similar).
Table 36. Motor cable sizes, 400—500 V
Chassis
Type
I
th
Motor cable
Cu [mm
2
]
Terminal cable size
Max. number of
cables/
Bolt size
Main
terminal
[mm
2
], max.
Earth terminal
[mm
2
]
CH3
0016_5
16
3*2.5+2.5
50
1—10
(Terminal block)
CH3
0022_5
22
3*4+4
50
1—10
(Terminal block)
CH3
0031
31
3*6+6
50
1—10
(Terminal block)
CH3
0038_5
0045_5
38—45
3*10+10
50 Cu
50 Al
6—35
(Terminal block)
CH3
0061_5
61
3*16+16
50 Cu
50 Al
6—35
(Terminal block)
CH4
0072_5
72
3*25+16
50 Cu
50 Al
6—70
1/M8
CH4
0087_5
87
3*35+16
50 Cu
50 Al
6—70
1/M8
CH4
0105_5
105
3*50+25
50 Cu
50 Al
6—70
1/M8
CH4
0140_5
140
3*70+35
95 Cu/Al
25—95
1/M8
CH5
0168_5
168
3*95+50
185 Cu/Al
25—95
2/M10
CH5
0205_5
205
3*150+70
185 Cu/Al
25—95
2/M10
CH5
0261_5
261
3*185+95
185 Cu/Al
25—95
2/M10
CH61
0300_5
300
2*(3*120+70)
*
25—185
2/M12
CH61
0385_5
385
2*(3*120+70)
*
25—185
2/M12
CH62/72
0460_5
460
2*(3*150+70)
**
25—185
4/M12
CH62/72
0520_5
520
2*(3*185+95)
**
25—185
4/M12
Содержание NX
Страница 1: ...vacon nx ac drives liquid cooled drives user manual ...