Control keypad
vacon • 127
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
7.3.4.3
Fault time data record
When a fault occurs the information described above in is displayed. By pushing the Menu button
right here you will enter the Fault time data record menu indicated by T.1
T.13. In this menu, some
selected important data valid at the time of the fault are recorded. This feature is intended to help
the user or the service person to determine the cause of fault.
The data available are:
Real time record
If real time is set to run on the AC drive the data items T1 and T2 will appear as follows:
7.3.5
Fault history menu (M5)
The Fault history menu can be entered from the Main menu by pushing the Menu button right when
the location indication M5 is visible on the first line of the keypad display. Find the fault codes in
Table 60.
All faults are stored in the Fault history menu in which you can browse through them using the
Browser buttons. Additionally, the Fault time data record pages are accessible at each fault. You can
return to the previous menu anytime by pushing the Menu button left.
The memory of the AC drive can store a maximum of 30 faults in the order of appearance. The
number of faults currently in the fault history is shown on the value line of the main page (H1
H#).
Table 52. Fault time recorded data
T.1
Counted operation days
(Fault 43: Additional code)
d
T.2
Counted operation hours
(Fault 43: Counted operation days)
hh:mm:ss
(d)
T.3
Output frequency
(Fault 43: Counted operation hours)
Hz
(hh:mm:ss)
T.4
Motor current
A
T.5
Motor voltage
V
T.6
Motor power
%
T.7
Motor torque
%
T.8
DC voltage
V
T.9
Unit temperature
°
C
T.10
Run status
T.11
Direction
T.12
Warnings
T.13
0-speed*
* Tells the user if the drive was at zero speed (< 0.01 Hz) when the fault occurred
T.1
Counted operation days
yyyy-mm-dd
T.2
Counted operation hours
hh:mm:ss,
sss