Hardware and Connections
2-25
7SJ63 Manual
C53000-G1140-C120-1
Direct Cable Connections: solid or stranded conductor with connector sleeve;
conductor with cross-section of 0.5 mm
2
to 3.3 mm
2
or AWG 20 to 12.
Use copper wires only!
Maximum Tightening Torque: 1.3 ft-lb or 16 in-lb (1.8 Nm).
Connections to
Current Terminals
Ring or spade lugs may be used. To maintain proper isolation of the circuits, the lugs
must be insulated or insulating sleeves must be fitted to cover the exposed crimp
zones.
The following must be observed:
Connections with Cable lugs: inner diameter of lugs, 5 mm;
maximum outer width of lugs, 12 mm;
conductor with cross-section of 2.7 mm
2
to 6.6 mm
2
or AWG 13 to 9.
Use copper wires only!
Cable lugs of series PIDG from AMP Co. are recommended, e.g.,
Ring cable lug: PIDG PN 130 171–0
Spade lug:
PIDG PN 326 865–0
Direct Cable Connections: solid or stranded conductor with connector sleeve;
copper conductor with cross-section of 2.0 mm
2
to 5.0 mm
2
or AWG 14 to 10.
Use copper wires only!
Maximum Tightening Torque: 2.0 ft-lb or 24 in-lb (2.7 Nm).
Short-Circuit Links
Short-circuit links are available for convenience in making terminal connections.
The links can be used to connect two terminals located on the same side of the termi-
nal block. Thus, if the 7SJ63 is the last device in the current transformer circuits, the
links provide a convenient way to terminate the circuits. The links are useful in con-
necting the neutral point of wye-connected VTs at the 7SJ63. The links can be useful
for other connections as well.
Each terminal can receive two links, one link and one cable lug, or one single wire.
The links meet the safety requirements for protection against electric shock.
There are two types of links, one for voltage connections and one for current connec-
tions. The links are illustrated in Figure 2-8.
Ordering information for the links is provided in Section A.1 in the Appendix.
Figure 2-25
Short-circuit Links for Voltage Connections and Current Connections
Short-Circuit Links for
Voltage Connections
Short-Circuit Links for
Current Connections
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...