Technical Data
10-8
7SJ63 Manual
C53000-G1140-C120-1
– High Voltage Test (routine test)
3.5 kVDC
only power supply and binary inputs
– High Voltage Test (routine test)
500 V (rms) AC
Only Isolated Communications
and Time Synchronization Interfaces
– Impulse Voltage Test (type test)
5 kV (peak): 1.2/50
µ
s: 0.5 Ws: 3 positive
All Circuits Except Communications
and 3 negative surges in intervals of 5 s
and Time Synchronization Interfaces,
Class
III
EMC Tests for Im-
munity (Type Tests)
Standards:
IEC 60255–6 and –22, (Product standards)
EN 50 082–2 (Generic standard)
DIN 57 435 Part 303 ANSI/IEEE C37.90.1
and C37.90.2
– High Frequency Test
2.5 kV (Peak): 1 MHz:
τ
= 15 ms;
IEC 60255–22–1, Class
III
400 Surges per s: Test Duration 2 s
and VDE 0435 Part 303, Class
III
R
i
=200
Ω
– Electrostatic Discharge
8 kV contact discharge: 15 kV air-
IEC 60255–22–2 Class
IV
discharge, both polarities:150 pF:R
i
=330
Ω
and IEC 61000–4–2, Class
IV
– Irradiation with HF Field,
10 V/m: 27 MHz to 500 MHz
non-modulated
IEC 60255–22–3 (Report) Class
III
– Irradiation with HF Field,
10 V/m: 80 MHz to1000 MHz: 80 % AM:
amplitude modulated
1 kHz
IEC 61000–4–3, Class
III
– Irradiation with HF Field,
10 V/m: 900 MHz: repetition frequency
Pulse Modulated
200 Hz: duty cycle of 50 %
IEC 61000–4–3/ENV 50204, Class
III
– Fast Transient Disturbance Variables/ 4 kV: 5/50 ns: 5 kHz: Burst length = 15 ms;
Burst IEC 60255–22–4 and
repetition rate 300 ms: both polarities:
IEc 61000-4-4, Class
IV
R
i
= 50
Ω
: Test Duration 1 min
– High Energy Surge Voltages
(SURGE), IEC 61000–4–5
Installation Class 3
Power Supply
common mode:
2 kV: 12
Ω
: 9
µ
F
diff. mode:
1 kV: 2
Ω
: 18
µ
F
Measuring Inputs, Binary Inputs
common mode:
2 kV: 42
Ω
: 0.5
µ
F
and Relay Outputs
diff. mode:
1 kV: 42
Ω
: 0.5
µ
F
– Line Conducted HF, amplitude modul. 10 V: 150 kHz to 80 MHz: 80 % AM: 1 kHz
IEC 61000–4–6, Class
III
– Power System Frequency Magnetic
30 A/m continuous: 300 A/m for 3 s: 50 Hz
Field IEC 61000–4–8, Class
IV
0.5 mT: 50 Hz
IEC 60255–6
– Oscillatory Surge Withstand Capability 2.5 to 3 kV (Peak Value): 1MHz to 1.5 MHz
ANSI/IEEE C37.90.1
damped wave: 50 surges per s:
duration 2 s: R
i
= 150
Ω
to 200
Ω
– Fast Transient Surge Withstand Cap. 4 kV to 5 kV: 10/150 ns: 50 Pulse per s;
ANSI/IEEE C37.90.1
both polarities: Duration 2 s: R
i
= 80
Ω
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...