Configuration
5-29
7SJ63 Manual
C53000-G1140-C120-1
Configuring CFC
as a Destination
Single point, double point, and output indications, as well as limit and measured val-
ues, may be configured to CFC as the destination.
Configuring the
Default Display and
Control Diagram
as a Destination
All information, including limit values, may be configured, both in the default and con-
trol display. By placing an
;
in the matrix cell, the information may be used within the
default and control control display. This feature is not available on the 7SJ61_62 se-
ries of relays.
Configuring Con-
trol Display as a
Destination for
Command Initiation
Single point and double point indications, transformer tap change indications, and all
types of commands may be configured to the control display as the destination. These
indications and commands then become available in the relay’s control display for op-
erational control.
Configuring the
Measured Value
Window as a
Destination
In addition to the measured values available in the relay, user defined measured and
limit values may be configured into the measured value window. These values then
become available in the device display in the assigned measurement window.
Configuring the
Metered Value
Window as a
Destination
In addition to the metered values available in the device, user defined pulse and me-
tered values derived from the measured values may be configured into the metered
value window so that they may be shown at the front display.
Retrieving Device
Configurations
from the Device
Front
Retrieving
the configurations is also possible from the device front. The user may ac-
cess configuration information
0DLQ0HQX
:
→
6HWWLQJV
→
0DVNLQJ,2
.
The menu title
0$6.,1*,2
appears in the title bar. Configuration information re-
garding each (physical) input and output is indicated in the display.
Protective Measurement Value
X
Protective Measurement Value with Time (MVT)
X
Protective Measurement Value, User Defined (MVU)
X
Pulsed Metered Value (PMV)
X
Metered Value from Measurement Value (MVMV)
X
Table 5-3
Overview of SCADA Interfaces
Information Type
↓
\SCADA Interface
→
Profibus
IEC
Warning!
CFC connection have to be reestablished after renaming of a display text of an user
defined information. Within the CFC the old name is shown at the left column. Delete
this connection. Make connection to the desired blocks using the renamed informa-
tion.
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...