Technical Data
10-28
7SJ63 Manual
C53000-G1140-C120-1
10.9
Motor Starting Protection (48)
Setting Ranges/In-
crements
Motor Starting Current
I
STARTUP
5.00 A to 80.00 A
1
) (Increments 0.05 A)
1
)
Pickup Threshold
I
MOTOR START
3.00 A to 50.00 A
1
)(Increments 0.05 A)
1
)
Permissible Starting Time T
STARTUP
1.0 to 180.0 s
(Increments 0.1 s)
Permissible Locked Rotor Time T
LOCKED-ROTOR
0.5 s to 120.0 s (Increments 0.1 s)
or
∞
(step is ineffective)
Trip Time Charac-
teristic
Dropout Ratio
I
rms
/
I
MOTOR START
approx. 0.95
Tolerance
Pickup Threshold
2 % of set value, or 50 mA
1
)
Time Delay
5 % or 30 ms
Influencing Values
for Pickup Thresh-
old
Power supply DC voltage (V
DC
) in range
0.8
≤
V
PS
/ V
PS nominal
≤
1.15
1%
Temperature in range
23º F
≤
ϑ
amb
≤
131º F
0.3% /10º F
Frequency in range
0.95
≤
f/f
N
≤
1.05
1%
Harmonics
- Up to 10% 3
rd
harmonic
1%
- Up to 10% 5
th
harmonic
1%
1
) for I
N
= 1 A, divide all limits by 5.
t
I
STARTUP
I
rms
------------------------
2
T
STARTUP
⋅
=
Trip Time Characteristics
I
STARTUP
Motor starting current setting.
I
rms
Actual current flowing.
I
MOTOR START
Pickup threshold setting,
used to detect motor startup.
t
Trip time in seconds.
for
I
rms >
I
MOTOR START
Where:
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...