Operators Tools
7-48
7SJ63 Manual
C53000-G1140-C120-1
From PC with
DIGSI
®
4
When the
2QOLQH
window in DIGSI
®
4 is opened with a double click, the operating
functions for the device appear in the left part of the window (Figure 7-37). Clicking on
&RQWUROV
brings up the function selection in the right side of the window (Figure 7-
46). By double clicking on
%UHDNHU6ZLWFKHV
, a dialog field is opened in which,
among other options, the option for interlocked and non-interlocked (Unlock) switching
is offered.
To switch operating resources without a check of the associated interlocking condi-
tions, mark the option
8QORFN
by clicking in that field
,
see section 7.3.1.
To set the switching mode for interlocked switching, the aforementioned option field
must not be marked. The marking is removed by clicking in the field again.
Further switching operations are possible until the dialog field
%UHDNHU6ZLWFKHV
is closed, or the switching mode is changed.
7.3.8
Control Messages
In the course of system control, the device generates several messages that docu-
ment the process. For example, messages may be given to report the end of a com-
mand or provide the reason for a command denial. These messages and the associ-
ated causes are listed in Table 7-4, together with other messages for the control of de-
vice functions.
DANGER!
Only highly qualified personnel who have an exact knowledge of the power sys-
tem conditions shall perform non-interlocked switching. Inappropriate switch-
ing operations can lead to death, serious personnel injury and property dam-
age.
:
Table 7-4
Possible Control Messages
Message Text
Message Cause
6\VWHP(UURU
Interruption by system error
0DQ2YHUZULWH2.
Return routing carried out
0DQ2YHUZULWH)DLO
Return routing cannot be carried out
&RQWURO$ERUW2.
Command interruption carried out correctly
&RQWURO$ERUW)DLO
Process cannot be interrupted because no command is issued,
command runs in different switching direction, or interruption is not
planned or set up.
&RQWURO([HFXWHG
Command was correctly executed and ended
&RQWURO)DLOHG
Refusal because the command number or the origination source is
not permitted
,QWHUORFNHG
Refusal because the communication interface was blocked or the
command object is blocked by a protective function.
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...