Configuration
5-39
7SJ63 Manual
C53000-G1140-C120-1
Figure 5-40
Warning message from DIGSI
®
4 when 100 % of allowed memory is used
After acknowledgement of the warning, the register sheet Compile under Option
→
5HSRUWV
can be accessed. By scrolling, an area can be reached in which statements
are given regarding the memory usage, as a percentage of the portion reserved for
CFC. In Figure 5-41 for example, an overload of 56 % is presented for the run-time
level PLC_BEARB (specially noted), while the other running levels are within the al-
lowed range.
Figure 5-41
Reading the loading level for CFC–diagrams
The following contains a few examples. A summary of the CFC configurations provid-
ed at the factory is shown in Appendix A.6.
Example 1 (MW):
Under Current
Set Points
(ANSI 37)
A configuration for low-current monitoring alarm (see Figure 5-42) which can be pro-
duced using CFC, should be a first example. This element may be used to detect op-
eration without load, or to recognize open circuited conditions. By connecting mea-
sured current values with a limit function via an “OR” function, an indication may be
generated which can be used to trip a circuit breaker.
•
The configuration sheet is assigned to run-time sequence MW_BEARB.
•
Four function modules (3-lower-value limit modules and an OR gate), are taken
from the function module library and copied into the configuration sheet.
•
In the left panel, the measurement values to be monitored (I
a
, I
b
, I
c
in % of the nom-
inal current) are each selected and connected with the measured value input of
each limit module function.
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...