Technical Data
10-40
7SJ63 Manual
C53000-G1140-C120-1
Waveform Capture
Maximum 8 fault records saved
Memory maintained by buffer
battery in case of loss of power supply
Recording Time
Total of 5 s
Pre-event and post-event recording
and memory time adjustable
Sampling Rate for 50 Hz
1 sample/1.25 ms (16 sam/cyc)
Sampling Rate for 60 Hz
1 sample/1.04 ms (16 sam/cyc)
Statistics (Circuit
Breaker)
Saved Number of Trips
Up to 9 digits
Accumulated Interrupted Current
Up to 4 digits (kA) per pole
Operating Hours
Counter
Operating Hours Range
Up to 7 digits
Criterion to Count
Current exceeds an adjustable current
threshold (BkrClosed
I
MIN)
Trip Circuit Monitor
(74TC)
With one or two binary inputs.
Commissioning
Start-up Aids
Phase Rotation Field Check
Operating Measured Values
Circuit Breaker / Switching Device Test
Creation of a Test Measurement Report
Clock
Time Synchronization
IRIG-B/DCF77-signal
Binary signal
Communication
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...