Functions
6-138
7SJ63 Manual
C53000-G1140-C120-1
7103
BLK MAN. CLOSE NO
YES
NO
Block automatic reclosing dur-
ing manual closing of breaker
(01 - BI)
X
X
X
7105 TIME RESTRAINT 0.50
~
320.00 sec. 3.00 sec.
Reset time of automatic reclos-
ing
X
X
X
7108 SAFETY 79 ready 0.01
~
300.00 sec. 15.00 sec.
Safety time until automatic re-
closing is ready
X
X
X
7113 CHECK CB?
No check
Chk each cycle
No check
Check breaker position indica-
tion before attempting a reclos-
ing shot
X
X
-
7115 CB TIME OUT
0.10
~
320.00 sec. 3.00 sec.
Breaker ready monitoring time
X
X
-
7116 MAX.InhibitTIME 0.01
~
320.00 sec. 15.00 sec.
Maximum inhibit time of auto re-
closing allowed for external bi-
nary input
-
X
X
7127 DEADTIME 1: PH 0.01
~
320.00 sec. 0.50 sec.
Dead Time 1, Phase Fault
X
X
X
7128 DEADTIME 1: G
0.01
~
320.00 sec. 0.50 sec.
Dead Time 1, Ground Fault
X
X
X
7129 DEADTIME 2: PH 0.01
~
320.00 sec. 0.50 sec.
Dead Time 2, Phase Fault
X
X
X
7130 DEADTIME 2: G
0.01
~
320.00 sec. 0.50 sec.
Dead Time 2, Ground Fault
X
X
X
7131 DEADTIME 3: PH 0.01
~
320.00 sec. 0.50 sec.
Dead Time 3, Phase Fault
X
X
X
7132 DEADTIME 3: G
0.01
~
320.00 sec. 0.50 sec.
Dead Time 3, Ground Fault
X
X
X
7133 DEADTIME 4: PH 0.01
~
320.00 sec. 0.50 sec.
Dead Time 4-9, Phase Fault
X
X
X
7134 DEADTIME 4: G
0.01
~
320.00 sec. 0.50 sec.
Dead Time 4-9, Ground Fault
X
X
X
7135 # OF RECL. GND
0
~
9
1
Number of reclosing attempts
for ground faults
X
X
X
7136 # OF RECL. PH
0
~
9
1
Number of reclosing attempts
for phase faults
X
X
X
7140 ZONE SEQ.CO-
ORD.
OFF
ON
OFF
Zone sequence coordination
-
X
X
7150 50–1/50N–1
No influence
Starts 79
Stops 79
No influence
50–1 and 50N–1 supervision of
automatic reclosing
X
X
X
7151 50–2/50N–2
No influence
Starts 79
Stops 79
No influence
50–2 and 50N–2 supervision of
automatic reclosing
X
X
X
7152 51/51N
No influence
Starts 79
Stops 79
No influence
51 and 51N supervision of auto-
matic reclosing
X
X
X
7153 67–1/67N–1
No influence
Starts 79
Stops 79
No influence
67–1 and 67N–1 supervision of
automatic reclosing
X
X
X
7154 67–2/67N–2
No influence
Starts 79
Stops 79
No influence
67–2 and 67N–2 supervision of
automatic reclosing
X
X
X
Addr.
LCD-Text
Setting Options
Default Setting
Comments
Ordering Code
7SJ63**–
**
A
**
–
**M
**–
**
B
**–
**
N
**–
**
C
**–
**
P*
*–
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...