SIPROTEC 4 Devices
4-25
7SJ63 Manual
C53000-G1140-C120-1
4.9
Display Editor
SIPROTEC
®
4 devices have a default display and — for a device with a graphical dis-
play and control functions — a control display. The default display appears automat-
ically after power-up. Operating information and measured values are typically shown.
A graphical display HMI also presents a single-line diagram of the primary equipment
being protected or controlled. The control display must be selected. The control dis-
play shows a single-line diagram with the primary control equipment that can be con-
trolled by the device. Control operations can be executed with this display. For clarity,
a control display typically contains less information than a default display.
4.9.1
Default Display
The default display is set at the factory according to the version of the device. The dis-
play provides the:
q
Present operating status of the switchgear device(s), and
q
Selected measured values.
Control operations cannot be done from the default display!
The layout of the display can be freely programmed. All information assigned in the
destination column of the configuration matrix for the default display can be shown.
The Display Editor program is used to modify the diagram in the display. See Figure
4-17.
4.9.2
Control Display
SIPROTEC
®
4 devices with graphical displays are delivered with a control display that
has default settings and a default layout.
Individual designs for the control display can be done. Catalogs of symbols, primary
equipment representations, and lines are available for designing. User-defined sym-
bols and user-defined primary equipment representations are simple to create with the
Display Editor. Each primary switchgear device has a different representation symbol
for the status (OPEN/CLOSE/INTERMEDIATE). The elements are easily assigned in
the Display Editor to design a new control display.
The zoom feature in the Display Editor can be used to enlarge the diagram to show
details, or reduce the diagram for an overview. The zoom feature also operates on the
catalog contents (symbols, representations, etc.).
Control operations can be initiated from the control display; therefore, the primary
switch representations must be dynamic. The representations must be configured in
the matrix to allow initiation of commands from the display and indication of static
equipment position. When using the Display Editor, the only information that is offered
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...