68
Function
Address
Content
AC motor drive
parameters
ggnnH
Gg: indicates parameter group; nn: indicates parameter. For
example: 0401H indicates parameter (4-01). Functions of
parameters shall see descriptions before for reference, when
catching parameter by from command code 03H, only one
parameter shall be got for each time.
Command(written
only )
2000H
bit 0-1
00: Blank
01: Stop reference
10: Run reference
11: JOG+RUN reference
bit 4-5
00: Blank
01: Fwd reference
10: REV reference
11: Changing direction
bit 2-3
bit 6-15
Not used
2001H
Frequency
reference
2002H
bit0
1. E.F. ON (External fault)
bit1
1 reset reference
bit2
Reserved
2003H
Reserved
Monitor status
(Reference read)
2100H
Error code
00: No fault records
01: oc ( over current)
02: ov (over voltage)
03: oh (over heating)
04: oL (drive over load)
05: oL1(Motor over load )
06: EF(external fault)
07: CPU writing fault (cf1)
08: Cf3 (CPU or analog circuit fault)
09: HPF (Hardware circuit fault)
10: ocA( over current in acceleration)
11: ocd(over current in deceleration)
12: ocn(over current in constant speed)
13: GFF (Grounding short circuit )
14: LV (low voltage)
15: Reserved
16: cf2( CPU read fault)
17: b.b
18: ol2 (over torque)
19: cfa ( auto accel/decel unavailable)
20: codE ( software code protection)