36
The acceleration time during motor acceleration and deceleration shall be the time used for
accelerating from 0Hz to Max operation frequency(1-00); while deceleration time refers to the time
for deceleration from Max operation frequency to 0Hz.
Applying the 2
nd
accel/decel time shall be available after the multi-functional terminals are set to
switching of 1
st
and 2
nd
accel/decel. 2
nd
accel/decel shall be performed when terminals for this
function are closed.
As diagram shows below, the motor adopts area of max operation frequency (1-00) from 0Hz for
acceleration and deceleration calculation, If 1-00 is 60.0Hz. Provided that min frequency is 1.0Hz,
time for accelerating to 60Hz shall be 9.83sec, and deceleration to stop shall also be 9.83sec.
中英文对照:
频率
FREQUENCY
加速时间
ACCELERATION TIME
减速时间
DECELERAION TIME
时间
TIME
实际加(减)速时间
Actual acceleration/deceleration time
加(减)速时间(操作频率
-
最低启动频率)
Acceleration/deceleration time (operation frequency –minimum starting
frequency)
最大操作频率
Max operation frequency
1-13
JOG acceleration time setting
Factory setting
d 10.0
Setting Range
d 0.01<->d 600s
Unit
0.01S
1-14
JOG deceleration time setting
Factory setting
d 10.0
Setting Range
d 0.01<->d 600s
Unit
0.01S
1-15
JOG frequency setting
Factory setting
d 6.0
Setting Range
d 1.0<->d 400Hz
Unit
0.01Hz
If switches connected with JOG function are CLOSED, AC motor drive shall accelerate from MIN
operation frequency (1-05) to jog operation frequency (1-15). Accel/decel time of jog run is
determined with reference time set by parameter (1-13/1-14). Jog run reference also can be
performed while AC motor driver is in operation. The AC motor driver will return to the original
operation frequency after canceling the jog-on command. But other operation commands can’t be
performed in jog operation.
频率:
Frequency
最大操作频率:
Max operation frequency
寸动频率:
Jog reference
时间:
Time
实际加速时间:
Actual acceleration time
寸动加速时间:
Jog acceleration time
寸动运转指令:
Jog run reference
1-16
Reserved
1-17
Reserved
1-18
Reserved