51
Wobble frequency function reset (d28):
Description of action: For both auto and manual selection of wobble frequency function, when this
terminal is closed, wobble frequency state information in memory shall be cancelled, and operation
frequency shall be preset; after opening the terminal, wobble frequency shall restart, and if it was
auto input mode, wobble frequency state shall only be available after wobble frequency delay time.
Inhibiting output (d29. d30):
This function provides the motor drive to receive emergency stop contactor from electrical system or
other fault signals without any fault output or RESET. After stop, operation shall only be available
after operation signal re-input, and driver shall restart from 0Hz.
Counter trigger signal input (d31): It shall not be used together with Parameter 0-04, 3-01 and 3-02
and if all set to 0, counting shall not vary.
Description of action: This function terminal TRG can use external triggering signals (e.g. signals
near switch, photoelectric inductors) to make inverter count. And control application based on
counting shall be completed by reference signal of multifunctional output terminals (counting
agreement, random counting agreement). Examples are coiling machine and packing machine.
4-09
Speed tracking after b.b. reset
Factory setting
d 0
Setting
range
d 0
Tracking downwards from speed before b.b
d 1
Tracking upwards from min speed
For detailed action description, see Parameter8-04.
4-10~4-22
Reserved
5. Multi-step and auto-program operation parameter
5-00
1
st
Step Speed
Factory setting
d 0.0
5-01
2
nd
Step Speed
Factory setting
d 0.0
5-02
3
rd
Step Speed
Factory setting
d 0.0
5-03
4
th
Step Speed
Factory setting
d 0.0
5-04
5
th
Step Speed
Factory setting
d 0.0
5-05
6
th
Step Speed
Factory setting
d 0.0
5-06
7
th
Step Speed
Factory setting
d 0.0
Setting range
d0.0<->d 400Hz
Unit
0.1Hz
Multi-step operation (8-step as maximum value) shall be available by means of multi-function
input terminals (see 4-04 to 4-08 for reference), the step speed frequency shall be set
respectively within a range of 5-00 to 5-06. Programming automatic operation shall be available in
coroperation to parameters (5-18 to 5-25).