72
A-02
Wobble Frequency Function selection
Factory setting
d 0.0
Setting range
d 0.0<->d 400Hz
Unit
0.1Hz
Operation frequency of the inverter prior to wobble frequency running status shall be determined
by this parameter.
A-03
Action delay setting of preset Wobble Frequency
Factory setting
d 0.00
Setting range
d 0.0<->d 600S
Unit
0.1Sec
When auto-restarting is in option, A-30 is to set the delay time running in preset frequency of
wobble frequency; and it shall be unavailable when inverter is set to manually control mode.
A-04
Central frequency option of Wobble Frequency
Factory setting
d 0
Setting range
d 0
According to operation frequency source
d 1
According to fixed frequency setting(A-05)
A-05
Fixed central frequency setting of Wobble Frequency
Factory setting
d 20.0
Setting range
d 0.01<->d 100%
(Corresponding Maximum
Frequency Operation)
Unit
0.1%
A-06
Reference source setting for wobble aptitude
Factory setting
d 0
Setting range
d 0
Relative central frequency
d 1
Relative Max operation frequency(1-00)
Wobble frequency running is limited by min and max setting. Fault shall occur if it is not set
properly.
A-07
wobble aptitude size setting
Factory setting
d 0.0
Setting range
d 0.0<->d 50.0%
Unit
0.1%
Wobble amplitude shall be calculated according to Parameter A-06.
A-08
wobble frequency hopping
Factory setting
d 0.0
Setting range
d 0.0<->d 50.0%
Unit
0.1%
When it is set to 0, it refers that no frequency hopping occurs.
A-09
Wobble frequency cycle
Factory setting
d 10.0
Setting range
d 0.1<->d 655S
Unit
0.1Sec
This parameter sets time for a complete work cycle including wobble rising and descending.
Never select auto acceleration/deceleration running cycle in wobble frequency running mode,
otherwise fault to wobble frequency cycle may occur.
A-10
Triangle wave rising time
Factory setting
d 50.0
Setting range
d 0.1<->d 99.9%
Unit
0.1%
This parameter sets operation time of wobble frequency rising, which is equivalent to
(A-09)×(A-10)(sec), and operation time of wobble frequency rising shall be (A-09)×(A-10)(sec).
A-11
wobble frequency machine stop starting mode
Factory setting
d 0
Setting range
d 0
Starting in memorizing state before machine stop
d 1
Restarting
A-12
wobble state power loss memory
Factory setting
d 0
Setting range
d 0
Memorizing
d 1
Non-memorizing
This parameter shall only be available when A-11 is set to 0(Starting in memorizing state before
machine stop)