34
0-07
Input parameter locking code
Factory setting
d 0
Setting range
d 0<->d 999
Description
of Display
d0
No code locking or correct code has been input
d1
Parameters have been locked
When this parameter indicates as d1, all parameters have been locked. Correct password must be
entered to make this parameter able to write. This parameter will display d0 after entering the
correct password. It will be locked again if incorrect password is entered.
After having entered the correct password, all parameters can be set before this interruption of
power supply. However, if the value of 0-08 isn’t cleared, which means the password protection
function hasn’t been cancelled, the correct password must be entered again to modify parameters
when power on next time. “End” will be displayed whether the parameter password is entered
correctly or not, otherwise “Err” will be displayed.
This password has three times of entering limit to prevent from entering password arbitrarily. If
enter wrong password three times continuously, “Err” will be displayed. It is necessary to reboot
the power supply to enter password again.
0-08
Input parameter locking code
Factory setting
d 0
Setting range
d 0<->d 999
Description
of Display
d0
Code not set
d1
Code set
This parameter is set to 0 when no code locking was set. All parameters shall be locked if it is set
to numbers other than 0. When this parameter is d1, modification of parameter will be displayed
“Err”. Decode the parameter through 0-07 to reset the new password.
0-09
Reserved
1. Basic Parameters
1-00
Max operation frequency setting
Factory setting
d 50.0
Setting range
d 5.0<->d 400Hz
Unit
0.1Hz
To set max operation frequency of the AC motor drive. Range of this frequency is corresponded to
digital operator frequency and all the other analog input frequency setting signals (0 to +10V, 4 to
20mA)
1-01
Max voltage frequency setting
Factory setting
d 50.0
Setting range
d 10.0<->d 400Hz
Unit
0.1Hz
This setting shall be in accordance with rated operation voltage frequency of the motor explained
on the nameplate.
1-02
Max output voltage setting
Factory setting
d 220*
Setting range
d 2.0<->d 255V*
Unit
0.1V
It is used to set Max output voltage of AC motor drive. This setting shall be in accordance with
rated voltage motor explained on the nameplate.