48
Function List
Set value
Function
Set
value
Function
d 0
No function
d 16
bb, normally closed(NC) input
d 1
MI1: forward run/stop, MI2: reverse
run/stop
d 17
UP COMMAND
d 2
MI1: run/stop, MI2: fwd/rev
d 18
DOWN COMMAND
d 3
Three line operation control(1): MI1
run,
MI2
fwd/rev
run,
MI3
STOP(Normally closed)
d 19
Program auto- operation reference
d 4
Three line operation control(1): MI1 run
(Triggering), MI2 run(Triggering), MI3
STOP(Normally closed)
d 20
Auto-program operation pause
d 5
EF, normally open interface input (N.O) d 21
JOG frequency reference
d 6
EF, normally closed interface input
(N.C)
d 22
Count reset
d 7
RESET reference
d 23
Reserved
d 8
Multi-step speed Reference 1
d 24
JOG-FWD
d 9
Multi-step speed Reference 2
d 25
JOG-REV
d 10
Multi-step speed Reference 3
d 26
Reserved
d 11
Reserved
d 27
Wobble frequency function input
d 12
frequency switch function
d 28
Wobble frequency state reset
d 13
Accel/decel inhibition reference
d 29
Inhibiting output (N.C)
d 14
Switching of 1
ST
and 2
nd
Accel/Decel
time
d 30
Inhibiting output (N.C)
d 15
bb, normally open (NO) input
d 31
counter trigger signal input
Explanation of functions:
No function (d0):
Description of action: No function terminal is set to isolate the external terminals, which shall be free
from fault action in unclear cause.
Operational terminals setting for external terminals (d1, d2, d3 and d4)
Two line operation control 1 (d1): Controlling parameter 4-04, terminal MI1 and MI2, in which MI1:
forward run/stop, MI2: reverse run/stop. When 4-04 is set as 1, function set by MI2 is invalid.
Two line operation control 2 (d2): Controlling parameter 4-04, terminal MI1 and MI2, in which MI1:
forward run/stop, MI2: reverse run/stop. When 4-04 is set as 2, function set by MI2 is invalid.
Three line operation control 1 (d 3): Controlling parameter 4-04, terminal MI1, MI2 and MI3, in which
MI1 run, MI2 fwd/rev run, MI3 STOP(Normally closed). When 4-04 is set as 3, function set by MI2
and MI3 is invalid. The wiring diagram is as follows.
Three Line Control (1)
上图中英对照:
运转:
FWD(running)
停止:
EF( stops)
(正转
/
反转)
:
REV (fwd/rev run)
公共端:
DCM (terminal common)
闭:运转,
CLOSED: run
开:停止,
OPEN: stops
闭合:反转,断开:正转:
CLOSED: reverse run, OPEN: forward run