4 LIST OF DESCRIPTIONS FOR FUNCTIONAL PARAMETERS
0
User’s parameter
set during running available
Parameter
Parameter functions
Setting range
Factory
setting
0-00
Machine Model
Recognition (Only for
Reading)
1:220V/0.2KW
Factory
setting
2:220V/0.4KW
3:220V/0.75KW
4: 220V/1.5KW
5: 220V/2.2KW
6~9: Reserved
10:440V/0.4KW
11:440V/0.75KW
12:440V /1.5KW
13:440V/2.2KW
14:440V/3.7KW
0-01
Rated Current Display for
AC Motor Drive (Only for
Reading)
220V/0.2KW:1.6A
Factory
setting
220V/0.4KW:2.5A
220V/0.75KW:4.2A
220V/1.5KW:7.5A
220V/2.2KW:11.0A
440V/0.4KW:1.5KW
440V/0.75KW:2.5KW
440V/1.5KW:4.2KW
440V/2.2KW:5.5A
440V/3.7KW:8.2A
0-02
Parameter Reset
0~20
:
no function
0
10: Parameter reset to factory setting
0-03
Machine ON Display
Selection
0: F(Display set frequency reference)
0
1: H(Display actual running frequency)
2: U (Display multi-function determination)
3: A(Display motor running current)
0-04
Determining
multifunctional display
0: Displaying output physical quantity(u) defined
by operators
0
1: Displaying count value (c)
2: Displaying program operation content (X=tt)
3: Displaying DC-BUS voltage(U)
4: Displaying output voltage (E)
5: Displaying rotating speed(r )
6: output frequency 2 (after slip compensation) (h)
7: consumed power (p)
0-05
Proportional constant
setting
0.1~160
1.0
0-06
Software Version
Only for reading
#.#
0-07
Input parameter locking
code
0~999
0
0-08
Setting parameter locking
code
0~999
0
0-09
Reserved