25
3 Output Function Parameters
Set during running available
Parameter
Parameter functions
Setting range
Factory setting
3-09
Multifunctional Output Terminal
1(MO1)
0: no function
1
1: Reference during operation
2:Reference for set frequency
agreement
3: Zero-speed reference
4: Over torque detection reference
5: Reference during BB
6: Reference for low voltage detection
7: AC Motor driver operation mode
8: Fault reference
9: Any frequency reaching indication
10: automatic operation indication
11: stage one operation finished
12: automatic operation finished
13: automatic operation pause
14: reach setting counting
15: reach specified counting
16: driver preparation finished
17: forward direction indication
18: reverse direction indication
19: forward/reverse direction indication
3-10
Reserved
3-11
Dead time setting of forward and
reverse
0.0-600 s
0.0
3-12
Cooling fan control
0: fan continuous running
0
1: run for 1 minute after pressing stop
key
2: operate/stop along with diver
3-13
Min. AVI input voltage
0.0~10.0V
0.00
3-14
Min. AVI input voltage corresponding
frequency
0.0~100%Fmax
0.0
3-15
Max. AVI input voltage
0.0~10.0V
10.0
3-16
Max. AVI input voltage corresponding
frequency
0.0~100%Fmax
100
3-17
Min. ACI input current
0.0~20.0mA
4.0
3-18
Min. ACI input current corresponding
frequency
0.0~100%Fmax
0.0
3-19
Max. ACI input current
0.0~20.0mA
20.0
3-20
Max. ACI input current corresponding
frequency
0.0~100%Fmax
100
3-21
reserved
3-22
reserved