23
2 Operation mode parameters Set during running available
Parameter
Parameter functions
Setting range
Factory setting
2-01
Auxiliary frequency input
source
0: Keyboard(OP) input
0
1: Input DC 0 to 10V by external terminals AVI
2: Input 4 to 20Ma by external terminals ACI
3: controlled by VR on digital controller
4: reserved
5: reserved
6: Controlled by UP/DOWN
7:Controlled by UP/DOWN (Frequency
memory)
8:reserved
2-02
Combination way of
frequency sources
0: Master frequency
0
1: Master fre Auxiliary frequency
2: Master frequency - Auxiliary frequency
2-03
Operation Reference Source
0: Operated by keyboard
0
1: Operated by external terminals. STOP on
keyboard available
2: Operated by external terminals. STOP on
keyboard unavailable
3: Operated by Communication Interface
RS-485. STOP on keyboard available
4: Operated by Communication Interface
RS-485. STOP on keyboard unavailable
2-04
STOP mode *
0: Deceleration and stop
0
1: Coast to a stop
2-05
Reserved
2-06
External fault EF stop mode
0: Reserved
1
1: EF free running to stop
2-07
AVI Zeroing stop mode
0: AVI Zeroing braking to stop
2
1: AVI Zeroing free running to stop
2: AVI Zeroing braking to stop and running
signals are reserved.
2-08
Reserved
2-09
PWM load wave frequency
setting
2.0~12.0khz
6.0
2-10
Operation direction inhibition
setting
0: Fwd/rev run available
0
1: Reverse run inhibited
2: Fwd run inhibited
2-11
ACI(4 to 20mA) broken line
treatment
0: Non-treatment to ACI broken line
0
1: Free operation stops when ACI line broken
2: Braking to stop displaying EF when ACI line
broken
3: Run in final set frequency when ACI line
broken
2-12
Power supply starting
operation locking
0: Operation available
0
1: Operation unavailable
2-13~2-14
reserved
Notes:
1) In 2-00 and 2-01, when 2-00 has been set as 1(AVI) or 2(ACI), 2-01 can’t be set as 1 or 2 again.