76
Inspection item
7 MAINTENANCE AND AMBIENT ELEMENTS
For safety and normal operation, the inverter shall be provided with daily as well as periodical
maintenance.
Diagram below shows items that must be checked.
Check shall again performed after the inverter is powered off for several minutes, to prevent
injury to operators caused by residual power of inverter condenser.
Inspection content
Inspection
period
Inspection method
Assessment
base
Corrective
measures to fault
Daily
Annual
Machine
ambient
environment
Verify ambient
temperature and
humidity
○
Measure with
temperature or
humidity meter in
accordance with notes
for installation
Temperature: -10
to 10
℃
; hum idity:
below 95%RH
Improve
environments
Check stacking
with inflammable
materials
○
View inspection
No foreign
materials
Inverter
installing and
grounding
Check abnormal
vibration to
machine
○
View and auditory
inspection
No foreign
materials
Tighten securing
screws
Check grounding
resistance
complies with
specification
○
Measure resistance
with three-functional
meter
220V Class:
below 100Ω
;
440V Class:
below 100Ω
Modify grounding
Input power
supply voltage
Check main circuit
voltage
○
Measure resistance
with three-functional
meter
Voltage value
complies with
specifications
Modify input
power supply
External
terminal
securing
screws of the
inverter
Check security of
screwed parts
○
View inspection and
check screws are
secured tightly with
screwdriver
All OK
Tighten or sent
for factory
maintenance and
overhaul
Check terminal
board is not
damaged
○
Check no clear
rust exists
○
Inverter inner
wiring
Check no
distortion appears
○
All OK
Check outer
shielding is not
broken
○
View inspection
All OK
Replace or sent
for factory
maintenance and
overhaul
Radiator
Check no dust or
chipping stacked
○
View inspection
All OK
Remove stacking
such as dust
Printing circuit
board
Check no
inductive metal or
oil stacked
○
View inspection
All OK
Remove or
replace electric
board
Check elements
are exclusive of
color changing or
burning due to
overheat
○
Cooling fan
Check abnormal
vibration or noise
○
View inspection and
auditory inspection
All OK
Replace cooling
fan
Check no dust or
chipping stacked
○
View inspection
Remove
Power
elements
Check no dust or
chipping stacked
○
View inspection
All OK
Remove
Check resistance
between terminals
○
Check using
three-functional meter
No short circuit or
circuit break for
three phase
output
Replace power
elements or
inverter
Condenser
Check for odor or
leakage
○
View inspection
All OK
Replace elec
condenser or
inverter
Check for
expansion or
distortion
○