62
9-04
Communication transmission format
Factory setting
d 0
Setting range
d 0
Modbus ASC
Ⅱ
M ode, D ata form at <8,N ,1>
d 1
Modbus ASC
Ⅱ
M ode, D ata form at <8,N ,2>
d 2
Modbus ASC
Ⅱ
M ode, D ata form at <8,E ,1>
d 3
Modbus ASC
Ⅱ
M ode, D ata form at <8,E ,2>
d 4
Modbus ASC
Ⅱ
M ode, D ata form at <8,O ,1>
d 5
Modbus ASC
Ⅱ
M ode, D ata form at <8,O ,2>
d 6
Modbus RTU Mode, Data format <8,N,2>
d 7
Modbus RTU Mode, Data format <8,E,1>
d 8
Modbus RTU Mode, Data format <8,O,1>
9
~
11
Reserved
9- 05
Reserved
9- 06
Reserved
9-07
Communication response delay time
Factory setting
d 1
Setting range
0
~
200 (one unit=2ms)
A period of time is needed to switch the host computer from sending state to receiving state. This
parameter can set the delay time to ensure the normal receiving of host computer.
变频器处理时间
inverter process time
响应延迟时间
response delay time
变频器回复数据
inverter recovery data
Computer control
For RS-485 series communication interface, each S1100 shall be prepared with individual
communication address in Parameter 9-00, thus inverter shall control it based on the individual
communication addresses.
S1100 AC motor drive is set to Modbus networks communication, and the following two modes are
available: ASC
Ⅱ
M ode( A m erican S tandard C ode for Inform ation Interchange) or R T U M ode ( R em ote
terminal Unit). Users can set specific mode and communication agreements in Parameter 9-04.
Code Meaning of Modes:
ASC
Ⅱ
M ode:
Each 8-bit data shall be consisted of two ASC
Ⅱ
characters. F or exam ple: a 1
-byte data 64H
(hexadecimal) shall be indicated as “64” by ASC
Ⅱ
code, consisting of “
6”
(36H ) and
“4” (34H)
Character symbol ‘0’
‘1’
‘2’
‘3’
‘4’
‘5’
‘6’
‘7’
ASC
Ⅱ
code
30H 31H 32H 33H 34H 35H 36H 37H
Character symbol ‘8’
‘9’
‘A’
‘B’
‘C’
‘D’
‘E’
‘F’
ASC
Ⅱ
code
38H 39H 41H 42H 43H 44H 45H 46H