28
5 Multi-step Speed and Auto-Program Operation Parameters Set during running available
Parameter
Parameter functions
Setting range
Factory setting
5-28
Reserved
5-29
Reserved
5-30
Reserved
5-31
Reserved
5-32
Reserved
5-33
Reserved
6 Protection Parameters Set during running available
Parameter
Parameter functions
Setting range
Factory setting
6-00
Over voltage stall prevention
function
0: Unavailable
370
740
220V series: 340V-400V
440 V series: 680V-800V
6-01
Over current stall prevention
level setting
0: Unavailable
170
20-200%
6-02
Over-torque detection function
option
0: No detection
0
1: Over torque detection (oL2) during constant
speed running, continue to run after detection.
2: Over torque detection (oL2) during constant
speed running, stop running after detection.
3: Over torque detection (oL2) during
acceleration, continue to run after detection.
4: Over torque detection (oL2) during
acceleration, stop running after detection.
6-03
Over torque detection level
30~200%
150
6-04
Over torque detection time
0.1~10.0S
0.1
6-05
Electrical thermal relay selection
0:No action
0
1:Act in standard motor
2:Act in special motor
6-06
Thermal relay action time
30~600S
60
6-07
Recent 1
st
fault record
0: No fault records
0
6-08
Recent 2
nd
fault record
1: oc ( over current)
0
6-09
Recent 3
rd
fault record
2: ov (over voltage)
0
6-10
Recent 4
th
fault record
3: oh (over heating)
0
6-11
Recent 5
th
fault record
4: oL (drive over load)
0
6-12
Recent 6
th
fault record
5 :oL1(Electrical thermal relay)
0
6: EF(external fault)
7: Reserved
8: Reserved
9: Reserved
10: Reserved
11: Reserved