Min. AVI input voltage
Factory setting
d 0.0
Setting range
d 0.0<-> d 10.0V
Unit
0.1V
3-14
Min. AVI input voltage corresponding frequency
Factory setting
d 0.0%
Setting range
d 0.0%<-> d 100% Fmax
Unit
0.1%
3-15
Max. AVI input voltage
Factory setting
d 10.0
Setting range
d 0.0<-> d 10.0V
Unit
0.1V
3-16
Max. AVI input voltage corresponding frequency
Factory setting
d 100%
Setting range
d 0.0%<-> d 100% Fmax
Unit
0.1%
These four parameters correspond to the condition when 2-00 or 2-01 is set as 1 (external terminal
AVI input DC 0
~
+10V).
3-17
Min. ACI input current
Factory setting
d 4.0
Setting range
d 0.0<-> d 20.0mA
Unit
0.1Ma
3-18
Min. ACI input current corresponding frequency
Factory setting
d 0.0%
Setting range
d 0.0%<-> d 100% Fmax
Unit
0.1%
3-19
Max. ACI input current
Factory setting
d 20.0
Setting range
d 0.0<-> d 20.0mA
Unit
0.1Ma
3-20
Max. ACI input current corresponding frequency
Factory setting
d 100%
Setting range
d 0.0%<-> d 100% Fmax
Unit
0.1%
These four parameters correspond to the condition when 2-00 or 2-01 is set as 2 (external terminal
AVI input DC 4
~
20mA).
The jumper cap has to switch to current ACI input (4
~
20mA).
Above eight parameters define the corresponding relationship between analog input voltage and
voltage/current.
Example:
输出频率
output frequency
模拟输入
analog input
3-21
Reserved
3-22
Reserved