57
7-02
Auto slip compensation setting
Factory setting
d 1
Setting range
d 0.0~d 1.0
Unit
0.1
This parameter can set AC motor drive to automatically output additional voltage when rotating in
order to get a higher torque. I .
7-03
Auto slip compensation setting
Factory setting
d 0.1
Setting range
d 0.0~d 10.0
Unit
0.1
Since load and slip shall increase when AC motor drives induction motor, this parameter( set value:
0.0-10.0) can set compensation frequency to decrease slip and provide the motor running speed
under rated current approach synchronous rotating speed. When output current of AC motor drive
exceeds motor no load current (7-01 set value), the motor drive shall compensate frequency in
accordance with this parameter.
7-04 ~7-10
Reserved
7-11
Motor rated revolution
Factory setting
d 1450
Setting range
d500<->d 3000
Unit
1
This parameter must be set up in accordance with the specifications in the nameplate of the motor.
7-12
Motor pole number
Factory setting
d 4
Setting range
D0<->d30
Unit
2
This parameter can set number of pole.( can’t be odd)
7-13
Motor rated power
Factory setting
d 50.0
Setting range
D 5.0<->d 400
Unit
0.1
This parameter must be set according to the nameplate specification of motor.
7-14~7-33
Reserved
Factory setting
8. High Function Parameters
8-00
DC braking level setting
Factory setting
d 0
Setting range
d 0<->d 100%
Unit
1%
Description of parameter: This parameter sets DC braking level of motor at starting or stopping;
braking capability shall increase as DC braking percentage increases. However, pay attention that
setting shall be increased gradually enough torque appear. And great care shall be given that this
braking percentage must be free from overlarge.